Enclosure Air Conditioner vs Heat Exchanger

Use an air-to-air heat exchanger when the plant air always stays at least 10°C (18°F) below the temperature the panel can run at. Use an enclosure air conditioner when the plant air gets that hot or hotter, because only a compressor can pull the panel below room temperature. Both keep the panel sealed, so both work in dirty, oily or wet air. The table below shows the trade, and the worked example shows how to size each one.

Request a QuoteBook 30 Minutes to Review the ApplicationCall 248-830-4850

Side by side

Air-to-air heat exchanger (PKS series) Enclosure air conditioner (DTS series)
How it cools Moves heat from the warm panel air to cooler room air through a sealed core. No compressor. Refrigerant loop with a compressor. Cools the panel below room temperature.
Works when room air is hotter than the panel target No Yes
Smallest temperature gap it needs About 10°C (18°F) room air below the target, per Pfannenberg None
Keeps dust, oil mist and moisture out Yes, closed loop Yes, closed loop
Power draw 75 W for the PKS 320X (fans only) Higher, the compressor runs too
Parts that wear Fans only Fans, compressor, refrigerant circuit
Condensate None made inside the panel Removes moisture, so plan a drain or evaporator
Size it by Watts per degree (W/°C) at your temperature gap BTU/hr at 95°F room and 95°F panel, then the curve at your hottest day
Ratings on this site NEMA 12, NEMA 3R/4, NEMA 4X stainless NEMA 12, NEMA 3R/4, NEMA 4/4X stainless

Worked example: 600 W panel, parts good to 104°F (40°C)

Step Math Result
Add 20% margin to the load 600 W × 1.2 720 W (2,457 BTU/hr)
Case A: room air tops out at 86°F (30°C) Gap = 40°C − 30°C 10°C, just enough for a heat exchanger
Heat exchanger size 720 W ÷ 10°C Pick a unit rated at 72 W/°C or more on the current Pfannenberg curve
Case B: room air hits 104°F or more Gap is 0 or less No heat exchanger or fan can work. Use an air conditioner
Air conditioner size 720 W × 3.412 2,457 BTU/hr at your hottest room temperature. The DTS 3061 and DTS 3081 are listed at 2,000 to 3,000 BTU/hr; we read the curve at your room temperature

Heat exchanger part numbers on this site

These are Pfannenberg PKS units sold under Hammond part numbers. Each family comes in 115 V, 230 V and 460 V; the last letters give the rating (LG = NEMA 12 gray, N4LG = NEMA 3R/4 gray, N4SS = NEMA 4X stainless).

Part number Family and rating Size H x W x D
PKS3042A115N4SS PKS Mini, NEMA 4X stainless 12 x 12 x 7.89 in
PKS3092A115N4SS PKS Mini, NEMA 4X stainless 22.75 x 12 x 7.89 in
PKS3131A115LG PKS 313X, NEMA 12 35 x 12 x 11 in
PKS3133A115N4LG PKS 313X, NEMA 3R/4 35 x 12 x 16 in
PKS3201A230LG PKS 320X, NEMA 12 35 x 12 x 11 in
PKS3204A460N4SS PKS 320X, NEMA 4X stainless 35 x 12 x 16 in
PKS3303A230N4LG PKS 330X, NEMA 3R/4 35 x 12 x 16 in
PKS3364A460N4SS PKS 336X, NEMA 4X stainless 35 x 12 x 16 in

Air conditioner part numbers on this site

Pfannenberg part Model BTU/hr
13383144255 DTS 3021, 115 V, NEMA 12 900 to 1,300
13382344355 DTS 3061, 115 V, NEMA 3R/4 2,000 to 3,000
13382341355 DTS 3061, 230 V, NEMA 3R/4 2,000 to 3,000
13382341300 DTS 3081, 230 V, NEMA 4/4X, 304 stainless 2,000 to 3,000

All 251 cooling units are in the air conditioner collection. Replacing a Hoffman, Rittal or Saginaw unit? Use the air conditioner cross reference.

Common questions

Can a heat exchanger cool the panel below room temperature?

No. It can only bring the panel close to room temperature, so the room must stay cooler than the target. If the room ever gets as hot as the panel target, you need an air conditioner.

Which one costs less to run?

The heat exchanger. The PKS 320X draws 75 W because only its fans run. An air conditioner runs a compressor on top of its fans.

What if the plant has chilled or process water?

An air-to-water heat exchanger like the Pfannenberg PWS series works even in very hot rooms, as long as the water is colder than the panel target. PWS units run from 650 W (2,218 BTU/hr) to 10,000 W (34,121 BTU/hr).

Is a Filterfan an option instead?

Only if the room air is clean. A Filterfan pulls room air through the panel. In dusty, oily or wet air, use a sealed heat exchanger or air conditioner. The enclosure cooling guide covers all three.

Does the cooling unit need the same NEMA rating as the box?

Yes. A NEMA 12 unit on a 4X box makes the panel a 12 at best. See NEMA 4 vs 4X vs 12.

Get it sized and quoted

Send the heat load in watts (or the drive horsepower), the hottest room temperature, the panel target and the NEMA rating. We send back the Pfannenberg model checked on the curve, with lead time.