Water and Wastewater Pump Motors, Drives and Panels
Deep well turbine pumps and vertical lift pumps take a vertical hollow shaft (VHS) motor with a non-reverse ratchet. Run it on a pump drive with built-in PID and pump cascade, and house the controls in a Type 4X panel with sealed cooling. Jobs paid with federal infrastructure money may also need Build America, Buy America (BABAA) listed parts. The tables below give the ratings and part numbers for each piece.
Request a QuoteBook 30 Minutes to Review the ApplicationCall 248-830-4850
Step 1: Pick the pump motor
| Motor | Enclosure | HP and speed | Voltage |
|---|---|---|---|
| TECO Westinghouse MAX-VHP / MAX-VH vertical hollow shaft, WPI, low voltage [VHP] | Weather Protected Type I | 7.5 to 800 HP, 1800 RPM | 230/460 V (150 HP and up 460 V only) |
| TECO Westinghouse MAX-VHP vertical hollow shaft, TEFC, low voltage [VHTP] | TEFC, IP55. CSA Class I, Div. 2, Groups B, C, D, T3 | 15 to 800 HP, 1800 and 1200 RPM | 230/460 V (150 HP and up 460 V only) |
| TECO Westinghouse vertical hollow shaft, WPI, medium voltage [VHKP] | Weather Protected Type I | 200 to 1,000 HP, 1800 and 1200 RPM | 2300/4000 V |
| TECO Westinghouse vertical hollow shaft, TEFC, medium voltage [VHKTP] | TEFC | 200 to 700 HP, 1800 and 1200 RPM | 2300/4000 V |
| TECO Westinghouse MAX-PE horizontal (end suction pumps, blowers, aeration) | TEFC, IP54 | 1 to 200 HP, 3600, 1800 and 1200 RPM | 230/460 V |
Standard on the TECO low voltage VHS motors: coupling with gib key, ball type non-reverse ratchet (NRR), drip and splash cover, 120 V space heaters, stainless nameplate, counterclockwise rotation viewed from the top, inverter duty per NEMA MG 1 Part 31 at 1.0 service factor. The WPI line adds rodent screens. 444TP to 449TP frames can be built for 175% high thrust. Sources: TECO Westinghouse VHS WPI and TEFC low voltage product descriptions, TECO vertical hollow shaft motor listing, MAX-PE product description.
Step 2: Pick the pump drive
The TECO Westinghouse F510 is TECO's fan and pump drive. TECO lists wastewater, irrigation and industrial pumping as target uses.
| F510 feature | What TECO lists |
|---|---|
| Range | 1 to 800 HP at 460 V and 1 to 150 HP at 230 V, variable torque |
| Pump cascade | Built in for up to 4 pumps (1 master, 3 followers). Up to 8 pumps with the JN5-IO-8D0 card |
| Process control | Two PID loops, switch by input or real time clock. Sleep mode |
| Communications | Modbus RTU, BACnet MS/TP and Metasys N2 on board (RS485 or RJ45) |
| Overload | 120% for 1 minute |
| Built for damp rooms | Conformal coating on all printed circuit boards |
| Motor protection | PTC input for direct motor thermal protection |
Common sizes on this site: F510-4025-C3-UE (25 HP), F510-4050-C3-UE (50 HP), F510-4100-C3-UE (100 HP) and F510-4215-C3-UE (200 HP).
On a VHS motor with a non-reverse ratchet, TECO rates the speed range at 10:1 variable torque. Without the ratchet and with braking in the drive, it is 20:1. Long cable runs out to a well or lift station need a check on carrier frequency and motor peak voltage. See long motor leads on a VFD and line reactor vs load reactor. A Rex 3PR-0060C3H is the 60 A, 3%, 480 V reactor for a 40 HP drive.
Sources: TECO Westinghouse F510 Fan and Pump AC Drive brochure and F510 product page. VHS speed range from the TECO VHS product descriptions. Rex HP rating from the Rex 480 V selection table.
Step 3: Outdoor panels, cooling and alarms
| Part | What it is | Rating |
|---|---|---|
| Stahlin J1210W | Fiberglass enclosure, 11.79 x 9.8 x 4.94 in, opaque cover | NEMA 4X |
| Hammond 1418N4S16B6 | Wallmount enclosure, 16 x 12 x 6 in, 316 stainless | Type 4X |
| Pfannenberg DTS 3081, 13382341159 | Air conditioner, 230 V, 750 W (2,000 to 3,000 BTU/hr), 316 stainless | NEMA 4/4X, BABAA listed |
| Pfannenberg DTS 3185, 13383639159 | Air conditioner, 230 V, 1,900 W (5,000 to 7,000 BTU/hr), 316 stainless | NEMA 4/4X, BABAA listed |
| Pfannenberg PATROL PA L 5, 23353158055 | RGB LED beacon with sounder, 107 dB, 115 VAC | High level and pump fail alarm |
Size the cooling with the heat load calculator and the enclosure cooling guide. Fiberglass or stainless? Both are Type 4X. See NEMA 4 vs 4X vs 12. All Stahlin boxes are in the Stahlin collection.
BABAA listed Pfannenberg units on this site
Pfannenberg lists these units as BABAA compliant: over 55% U.S. sourced content, assembled in Lancaster, NY. Ask for the Pfannenberg BABAA certificate with the quote.
| Part number | Model | Voltage | Capacity | Material |
|---|---|---|---|---|
| 13382344159 | DTS 3081 | 115 V | 750 W | 316 stainless |
| 13382341159 | DTS 3081 | 230 V | 750 W | 316 stainless |
| 13382336159 | DTS 3081 | 460 V | 750 W | 316 stainless |
| 13382344300 | DTS 3081 | 115 V | 750 W | 304 stainless |
| 13385444159 | DTS 3181 | 115 V | 1,300 W | 316 stainless |
| 13385441159 | DTS 3181 | 230 V | 1,300 W | 316 stainless |
| 13385436159 | DTS 3181 | 460 V | 1,300 W | 316 stainless |
| 13383436158 | DTS 3181 SL | 460 V | 1,500 W | 304 stainless |
| 13383644159 | DTS 3185 | 115 V | 1,900 W | 316 stainless |
| 13383639159 | DTS 3185 | 230 V | 1,900 W | 316 stainless |
| 13383636159 | DTS 3185 | 460 V | 1,900 W | 316 stainless |
Source: Pfannenberg USA BABAA product list and June 2025 BABAA compliance statement. Pfannenberg also lists select PKS air-to-air and PWS air-to-water heat exchangers. All listed DTS units are NEMA 4/4X. Ask for the current list before you bid.
Common questions
What does the non-reverse ratchet do?
It stops the shaft from spinning backward when the pump stops and the water column drains back down the column pipe. TECO ships a ball type NRR as standard on its low voltage VHS motors.
Can a vertical hollow shaft motor run on a VFD?
Yes. TECO rates its VHS motors inverter duty per NEMA MG 1 Part 31 at a 1.0 service factor. With the ratchet in place the range is 10:1 variable torque.
WPI or TEFC?
TECO builds both. The WPI line starts at 7.5 HP. The TEFC line starts at 15 HP, is IP55 and carries CSA Class I, Div. 2 for Groups B, C and D. Pick TEFC when the motor sits in a classified or dirty area.
How many pumps can one F510 run?
Up to 4 with the built-in cascade: one master and up to 3 followers. Add the JN5-IO-8D0 card for up to 8.
Which cooling units meet BABAA?
Pfannenberg lists select DTS 3081, 3181, 3185, 3281 and 3285 cooling units plus select PKS and PWS heat exchangers. The table above shows the ones on this site.
Get the station quoted
Send the pump HP, speed, thrust and voltage, the number of pumps, the cable length to the motor and the panel size. We send back the TECO motor and drive, reactors, enclosure and cooling as one quote with lead times.
Request a QuoteBook 30 Minutes to Review the ApplicationCall 248-830-4850