How to Pick a Power Distribution Block for a UL 508A Feeder

On a UL 508A feeder circuit, use a UL Listed power distribution block. It is listed to UL 1953, so the block itself meets the UL 508A feeder terminal spacing. Then pick it in four steps: the amp rating, the line conductor, the load taps per pole, and the wire metal. A UL Recognized power terminal block is a component listed to a different standard, and Marathon points feeder work to its listed series.

Request a QuoteBook 30 Minutes to Review the Application

Listed or Recognized: what Marathon says

UL Listed power distribution block UL Recognized power terminal block
Standard UL 1953 UL 1059 and CSA C22.2 No. 158
Voltage Marathon lists 600 V. The 152 series on this site is rated 1000 V in the Marathon selector 600 V spacing for application classes B and C
UL 508A feeder spacing Yes. Marathon says listed blocks can be used in all applications because they exceed the spacing requirements Marathon points feeder circuits to its listed blocks. Ask us for the listed match
Intended use Load side of service equipment, per NFPA 70 (NEC) Ask us for the use your panel listing allows
Marathon open series on this site 134, 135, 145 and 152 133, 135x601, 135x605, 141 and 144

Pick it in four steps

Step Do this
1. Amps Pick a block rated at or above the feeder. On this site the 152 series is 175 A, the 134 series runs 200 to 620 A, the 145 series 380 to 840 A, and the 135 series 475 and 950 A.
2. Line conductor Match the line side to the feeder wire and count. Example: two 500 kcmil per phase needs two line openings that take 500 kcmil, like the 145x301 or 145x992.
3. Load taps Count the branch conductors per phase and their sizes. Pick a layout with enough openings. The open blocks on this site run from 1 to 48 load openings per pole.
4. Wire metal Aluminum connector blocks on these pages take copper or aluminum wire where Marathon lists both ranges. The copper connector 145x986 and 145x992 list an aluminum range on the 2 and 3 pole only. Check the aluminum row on each part page.

Open blocks on this site, by rating

Rating 3-pole example Line side (copper) Load side per pole UL
175 A 1523570 2/0 to #12 AWG 4 taps, #4 to #14 AWG (aluminum connector) Listed
175 A 1523970 2/0 to #14 AWG 4 taps, #4 to #14 AWG (copper connector) Listed
175 A 1523572 2/0 to #14 AWG Splicer, in and out Listed
200 A 1343572 3/0 to #14 AWG Splicer, in and out Listed
380 A 1453552 500 kcmil to #4 AWG, 1 opening 12 taps, #2 to #14 AWG Listed
420 A 1343585 600 kcmil to #2 AWG 8 taps Listed
420 A 1343595 600 kcmil to #2 AWG 12 taps Listed
475 A 1353701 750 kcmil to 1/0 AWG, 1 opening Splicer, 1 out Listed
620 A 1343526 350 kcmil to #6 AWG, 2 openings 6 taps, 2/0 to #14 AWG Listed
620 A 1343350 350 kcmil to #6 AWG, 2 openings 2 out Listed
760 A 1453301 500 kcmil to #4 AWG, 2 openings 2 out Listed
760 A 1453992 500 kcmil to #4 AWG, 2 openings 12 taps, #2 to #14 AWG Listed
760 A 1453599 500 kcmil to #4 AWG, 1 opening Stud: two 3/8-16 studs for crimp lugs or bus bar Listed
760 A 1453610 500 kcmil to #4 AWG, 2 openings Stud: one 1/2-13 stud for crimp lugs or bus bar Listed
410 A 1453606 Stud: one 1/2-13 stud for crimp lugs or bus bar Stud: one 1/2-13 stud (copper connector) Listed
760 A 1453282 Stud: two 3/8-16 studs for crimp lugs or bus bar 8 taps, 2/0 to #14 AWG Listed
840 A 1453411 600 kcmil to #2 AWG, 2 openings 4 taps 3/0 to #6 and 4 taps #4 to #14 AWG Listed
950 A 1353703 750 kcmil to 1/0 AWG, 2 openings 6 taps, 250 kcmil to #6 AWG Listed without cover
950 A 1353708 750 kcmil to 1/0 AWG, 2 openings 8 taps, 3/0 to #6 AWG Listed without cover
950 A 1353704 750 kcmil to 1/0 AWG, 2 openings 10 taps, 2/0 to #14 AWG Listed without cover
950 A 1353702 750 kcmil to 1/0 AWG, 2 openings Splicer, 2 out Listed without cover
950 A 1353706 750 kcmil to 1/0 AWG, 2 openings 9 taps: 5 at 250 kcmil to #6 and 4 at #2 to #14 AWG Listed without cover
950 A 1353705 750 kcmil to 1/0 AWG, 2 openings 15 taps: 3 at 250 kcmil to #6 and 12 at #2 to #14 AWG Listed without cover
950 A 1353707 750 kcmil to 1/0 AWG, 2 openings 16 taps: 4 at 3/0 to #6 and 12 at #2 to #14 AWG Listed without cover
115 A 1413300 #2 to #14 AWG Splicer, in and out Recognized
115 A 1413400 #2 to #14 AWG 4 taps, #10 to #18 AWG Recognized
310 A 1333558 350 kcmil to #6 AWG Stud: one M10 stud for crimp lugs or bus bar Recognized
310 A 1333559 350 kcmil to #6 AWG Stud: one 3/8-16 stud for crimp lugs or bus bar Recognized
310 A 1333563 Stud: one 3/8-16 stud Stud: one 3/8-16 stud (copper connector) Recognized
310 A 1333564 Stud: one M10 stud Stud: one M10 stud (copper connector) Recognized
410 A 1333611 Stud: one 1/2-13 stud Stud: one 1/2-13 stud (copper connector) Recognized
380 A 1443569 500 kcmil to #4 AWG Stud: two 1/4-20 studs for crimp lugs or bus bar Recognized
420 A 1333565 600 kcmil to #2 AWG 2 taps, 250 kcmil to #6 AWG Recognized
420 A 1353601 600 kcmil to #2 AWG 24 taps, #4 to #14 AWG Recognized
950 A 1353605 600 kcmil to #2 AWG, 2 openings 4 taps, 350 kcmil to #6 AWG Recognized

Common questions

Can I use a UL Recognized terminal block on a UL 508A feeder?

Marathon builds its listed blocks for that job. Its catalog says listed power distribution blocks provide the UL 508A feeder terminal spacing and can be used in all applications. For a feeder, pick a listed block such as the 134, 135, 145 or 152 series. If a drawing calls out a recognized 133 block on a feeder, send it and we match a listed 134 block. For a recognized 132 block at 175 A, the listed match is the 152 series with the same wire ranges.

What is the largest open power block on this site?

The 135 series at 950 A, 600 V. The 135x703, 135x708 and 135x704 take two 750 kcmil to 1/0 AWG conductors per pole and split to 6, 8 or 10 load openings. The 135x706, 135x705 and 135x707 split to 9, 15 or 16 openings of mixed sizes, and the 135x702 is a 950 A splicer with two in and two out. Buy them without the CH1351 cover to keep the UL Listing; with the cover Marathon lists them as UL Recognized (cURus). The largest 145 block is the 145x411 at 840 A.

How do I read a Marathon open block number?

The fourth digit is the pole count. 1453411 is the 3-pole 145x411, 1451411 is the 1-pole. The last three digits set the connector layout.

Which Marathon blocks take a crimp lug or a bus bar on the load side?

The stud blocks. The load side is a threaded stud instead of a box connector, so a lugged cable or a bus bar tab bolts on. For a UL 508A feeder, the listed 145x599 (two 3/8-16 studs per pole) and 145x610 (one 1/2-13 stud per pole, two 500 kcmil line openings) are rated 760 A. The recognized 133x558 (M10 stud) and 133x559 (3/8-16 stud) are 310 A, and the 144x569 (two 1/4-20 studs) is 380 A. At 175 A the 132 series has M6 and 1/4-20 stud versions. For studs on both sides, the listed 145x606 is 410 A with one 1/2-13 stud per side. The recognized 133x563 (3/8-16) and 133x564 (M10) are 310 A, and the 133x611 (1/2-13) is 410 A. The listed 145x282 turns it around: two 3/8-16 studs on the line side and eight 2/0 to #14 AWG taps per pole, at 760 A.

Do these blocks take aluminum wire?

Most do. The aluminum connector blocks list both copper and aluminum wire ranges. Some layouts list no aluminum range on one pole count. Each part page shows the aluminum row, and where Marathon lists none, ask us before you use aluminum.

Get it picked and quoted

Send the feeder amps, the line wire size and count per phase, and the branch wire list. We send back the Marathon block, the cover part number and a quote.

Request a QuoteBook 30 Minutes to Review the Application

Related: Marathon collection · Mersen to Marathon power block cross reference · EPB enclosed power blocks · All cross references