On a UL 508A feeder circuit, use a UL Listed power distribution block. It is listed to UL 1953, so the block itself meets the UL 508A feeder terminal spacing. Then pick it in four steps: the amp rating, the line conductor, the load taps per pole, and the wire metal. A UL Recognized power terminal block is a component listed to a different standard, and Marathon points feeder work to its listed series.
Request a QuoteBook 30 Minutes to Review the Application
Listed or Recognized: what Marathon says
| UL Listed power distribution block | UL Recognized power terminal block | |
|---|---|---|
| Standard | UL 1953 | UL 1059 and CSA C22.2 No. 158 |
| Voltage | Marathon lists 600 V. The 152 series on this site is rated 1000 V in the Marathon selector | 600 V spacing for application classes B and C |
| UL 508A feeder spacing | Yes. Marathon says listed blocks can be used in all applications because they exceed the spacing requirements | Marathon points feeder circuits to its listed blocks. Ask us for the listed match |
| Intended use | Load side of service equipment, per NFPA 70 (NEC) | Ask us for the use your panel listing allows |
| Marathon open series on this site | 134, 135, 145 and 152 | 133, 135x601, 135x605, 141 and 144 |
Source: Marathon Special Products 2026 catalog, Standards and UL 1953 spacing pages. Marathon's UL 508A feeder circuit row names the EPB, 134, 135 and 145 series as listed power distribution blocks. Check the label on the block you order.
Pick it in four steps
| Step | Do this |
|---|---|
| 1. Amps | Pick a block rated at or above the feeder. On this site the 152 series is 175 A, the 134 series runs 200 to 620 A, the 145 series 380 to 840 A, and the 135 series 475 and 950 A. |
| 2. Line conductor | Match the line side to the feeder wire and count. Example: two 500 kcmil per phase needs two line openings that take 500 kcmil, like the 145x301 or 145x992. |
| 3. Load taps | Count the branch conductors per phase and their sizes. Pick a layout with enough openings. The open blocks on this site run from 1 to 48 load openings per pole. |
| 4. Wire metal | Aluminum connector blocks on these pages take copper or aluminum wire where Marathon lists both ranges. The copper connector 145x986 and 145x992 list an aluminum range on the 2 and 3 pole only. Check the aluminum row on each part page. |
Open blocks on this site, by rating
| Rating | 3-pole example | Line side (copper) | Load side per pole | UL |
|---|---|---|---|---|
| 175 A | 1523570 | 2/0 to #12 AWG | 4 taps, #4 to #14 AWG (aluminum connector) | Listed |
| 175 A | 1523970 | 2/0 to #14 AWG | 4 taps, #4 to #14 AWG (copper connector) | Listed |
| 175 A | 1523572 | 2/0 to #14 AWG | Splicer, in and out | Listed |
| 200 A | 1343572 | 3/0 to #14 AWG | Splicer, in and out | Listed |
| 380 A | 1453552 | 500 kcmil to #4 AWG, 1 opening | 12 taps, #2 to #14 AWG | Listed |
| 420 A | 1343585 | 600 kcmil to #2 AWG | 8 taps | Listed |
| 420 A | 1343595 | 600 kcmil to #2 AWG | 12 taps | Listed |
| 475 A | 1353701 | 750 kcmil to 1/0 AWG, 1 opening | Splicer, 1 out | Listed |
| 620 A | 1343526 | 350 kcmil to #6 AWG, 2 openings | 6 taps, 2/0 to #14 AWG | Listed |
| 620 A | 1343350 | 350 kcmil to #6 AWG, 2 openings | 2 out | Listed |
| 760 A | 1453301 | 500 kcmil to #4 AWG, 2 openings | 2 out | Listed |
| 760 A | 1453992 | 500 kcmil to #4 AWG, 2 openings | 12 taps, #2 to #14 AWG | Listed |
| 760 A | 1453599 | 500 kcmil to #4 AWG, 1 opening | Stud: two 3/8-16 studs for crimp lugs or bus bar | Listed |
| 760 A | 1453610 | 500 kcmil to #4 AWG, 2 openings | Stud: one 1/2-13 stud for crimp lugs or bus bar | Listed |
| 410 A | 1453606 | Stud: one 1/2-13 stud for crimp lugs or bus bar | Stud: one 1/2-13 stud (copper connector) | Listed |
| 760 A | 1453282 | Stud: two 3/8-16 studs for crimp lugs or bus bar | 8 taps, 2/0 to #14 AWG | Listed |
| 840 A | 1453411 | 600 kcmil to #2 AWG, 2 openings | 4 taps 3/0 to #6 and 4 taps #4 to #14 AWG | Listed |
| 950 A | 1353703 | 750 kcmil to 1/0 AWG, 2 openings | 6 taps, 250 kcmil to #6 AWG | Listed without cover |
| 950 A | 1353708 | 750 kcmil to 1/0 AWG, 2 openings | 8 taps, 3/0 to #6 AWG | Listed without cover |
| 950 A | 1353704 | 750 kcmil to 1/0 AWG, 2 openings | 10 taps, 2/0 to #14 AWG | Listed without cover |
| 950 A | 1353702 | 750 kcmil to 1/0 AWG, 2 openings | Splicer, 2 out | Listed without cover |
| 950 A | 1353706 | 750 kcmil to 1/0 AWG, 2 openings | 9 taps: 5 at 250 kcmil to #6 and 4 at #2 to #14 AWG | Listed without cover |
| 950 A | 1353705 | 750 kcmil to 1/0 AWG, 2 openings | 15 taps: 3 at 250 kcmil to #6 and 12 at #2 to #14 AWG | Listed without cover |
| 950 A | 1353707 | 750 kcmil to 1/0 AWG, 2 openings | 16 taps: 4 at 3/0 to #6 and 12 at #2 to #14 AWG | Listed without cover |
| 115 A | 1413300 | #2 to #14 AWG | Splicer, in and out | Recognized |
| 115 A | 1413400 | #2 to #14 AWG | 4 taps, #10 to #18 AWG | Recognized |
| 310 A | 1333558 | 350 kcmil to #6 AWG | Stud: one M10 stud for crimp lugs or bus bar | Recognized |
| 310 A | 1333559 | 350 kcmil to #6 AWG | Stud: one 3/8-16 stud for crimp lugs or bus bar | Recognized |
| 310 A | 1333563 | Stud: one 3/8-16 stud | Stud: one 3/8-16 stud (copper connector) | Recognized |
| 310 A | 1333564 | Stud: one M10 stud | Stud: one M10 stud (copper connector) | Recognized |
| 410 A | 1333611 | Stud: one 1/2-13 stud | Stud: one 1/2-13 stud (copper connector) | Recognized |
| 380 A | 1443569 | 500 kcmil to #4 AWG | Stud: two 1/4-20 studs for crimp lugs or bus bar | Recognized |
| 420 A | 1333565 | 600 kcmil to #2 AWG | 2 taps, 250 kcmil to #6 AWG | Recognized |
| 420 A | 1353601 | 600 kcmil to #2 AWG | 24 taps, #4 to #14 AWG | Recognized |
| 950 A | 1353605 | 600 kcmil to #2 AWG, 2 openings | 4 taps, 350 kcmil to #6 AWG | Recognized |
Ratings from the Marathon Special Products power block selector (marathonsp.com) and each part page. Every block above is 600 V except the 152 series, rated 1000 V. "Listed without cover" means Marathon lists the 135x702 to 135x708 blocks as UL Listed when bought without the CH1351 cover and UL Recognized (cURus) with it. The 141 series also comes in 4 pole (1414300, 1414400, 1414301, 1414205). 1 and 2 pole versions are on the Marathon collection.
Common questions
Can I use a UL Recognized terminal block on a UL 508A feeder?
Marathon builds its listed blocks for that job. Its catalog says listed power distribution blocks provide the UL 508A feeder terminal spacing and can be used in all applications. For a feeder, pick a listed block such as the 134, 135, 145 or 152 series. If a drawing calls out a recognized 133 block on a feeder, send it and we match a listed 134 block. For a recognized 132 block at 175 A, the listed match is the 152 series with the same wire ranges.
What is the largest open power block on this site?
The 135 series at 950 A, 600 V. The 135x703, 135x708 and 135x704 take two 750 kcmil to 1/0 AWG conductors per pole and split to 6, 8 or 10 load openings. The 135x706, 135x705 and 135x707 split to 9, 15 or 16 openings of mixed sizes, and the 135x702 is a 950 A splicer with two in and two out. Buy them without the CH1351 cover to keep the UL Listing; with the cover Marathon lists them as UL Recognized (cURus). The largest 145 block is the 145x411 at 840 A.
How do I read a Marathon open block number?
The fourth digit is the pole count. 1453411 is the 3-pole 145x411, 1451411 is the 1-pole. The last three digits set the connector layout.
Which Marathon blocks take a crimp lug or a bus bar on the load side?
The stud blocks. The load side is a threaded stud instead of a box connector, so a lugged cable or a bus bar tab bolts on. For a UL 508A feeder, the listed 145x599 (two 3/8-16 studs per pole) and 145x610 (one 1/2-13 stud per pole, two 500 kcmil line openings) are rated 760 A. The recognized 133x558 (M10 stud) and 133x559 (3/8-16 stud) are 310 A, and the 144x569 (two 1/4-20 studs) is 380 A. At 175 A the 132 series has M6 and 1/4-20 stud versions. For studs on both sides, the listed 145x606 is 410 A with one 1/2-13 stud per side. The recognized 133x563 (3/8-16) and 133x564 (M10) are 310 A, and the 133x611 (1/2-13) is 410 A. The listed 145x282 turns it around: two 3/8-16 studs on the line side and eight 2/0 to #14 AWG taps per pole, at 760 A.
Do these blocks take aluminum wire?
Most do. The aluminum connector blocks list both copper and aluminum wire ranges. Some layouts list no aluminum range on one pole count. Each part page shows the aluminum row, and where Marathon lists none, ask us before you use aluminum.
Get it picked and quoted
Send the feeder amps, the line wire size and count per phase, and the branch wire list. We send back the Marathon block, the cover part number and a quote.
Request a QuoteBook 30 Minutes to Review the Application
Related: Marathon collection · Mersen to Marathon power block cross reference · EPB enclosed power blocks · All cross references