The Block LR3 48-3/500 is a 3 phase line reactor rated 500 A at 480 V with 3% impedance (0.044 mH per phase). Block USA's cross reference puts it on 350 to 400 HP drives at 480 V. It is UL 508 Listed and cULus marked, open frame (IP00), with copper windings, class H insulation and flat copper terminals. Applied Control is the Block manufacturers representative. Send the catalog number, or the drive HP, voltage and impedance you need, and we send back a quote.

Request a QuoteBook 30 Minutes to Review the Application

LR3 48-3/500 specifications

Catalog number LR3 48-3/500
Manufacturer Block Transformatoren-Elektronik (Block USA)
Series LR3 line reactor, 3 phase
Rated current 3 x 500 A AC
Linear current 3 x 750 A AC
Inductance 3 x 0.044 mH
Impedance (short circuit voltage) 3% at 480 V
Rated voltage 480 V (voltage range 0 to 690 V)
Frequency 50 to 60 Hz
NEC HP at 480 V (Block USA cross reference) 350 to 400 HP
Motor power, IEC (Block catalog) 315 kW (422.42 HP)
Insulation class H (180 C)
Protection IP00, open core and coil, mount inside an enclosure
Ambient temperature -10 to 40 C (14 to 104 F)
Terminals Flat copper connection for line and load, bolt connection for ground
Winding material Copper
Dimensions (W x H x D) 352 x 265 x 184 mm (13.86 x 10.43 x 7.24 in)
Weight 54.37 kg (119.9 lb)
Standards and listings UL 508 Listed, cULus, EN 61558-2-20, RoHS (EN IEC 63000)

Specifications from the Block product page for LR3 48-3/500. Confirm against the current datasheet before installation.

Block product page and datasheet for LR3 48-3/500

Cross reference for LR3 48-3/500

These 3% impedance, 480 V reactors cross to the LR3 48-3/500 on the Block USA cross reference table. Send any of these part numbers and we quote the Block part. See the full line reactor cross reference.

Rockwell Automation 1321 1321-3R500-B
MTE RL-50002
TCI KDR KDRULJ2L, LDRULJ1L
TCI KLR KLRUL420APT, KLRUL480APT
Acme ALRB-420CBC, ALRB-480CBC
Hammond Power CRX0414AC, CRX0477AC

The cross reference matches electrical ratings only. Check dimensions, mounting holes and terminal type before you swap a reactor in an existing panel.

3% or 5%?

A 3% reactor on the drive input cuts line notching and nuisance overvoltage trips and is the usual default. A 5% reactor cuts input current harmonics further and gives more protection when the supply is stiff or has capacitor switching upstream. On the output side, a reactor slows voltage rise at the motor on longer lead runs. Send the drive model and motor lead length and we will size it with you. See the Block collection, Rex Power Magnetics reactors, TECO AC drives and the cross reference hub.

Request a QuoteBook 30 Minutes to Review the Application

Rockwell Automation, Allen-Bradley, MTE, TCI, Acme and Hammond Power Solutions are trademarks of their respective owners. Applied Control Inc. is not affiliated with these companies. Competitor names appear only to identify products for comparison.