3PR-0002C5H | Rex Power Magnetics 2 A 5% Line/Load Reactor, 480/600 V
Couldn't load pickup availability
Questions or Require Additional Information?
Call us Today at +1-248-830-4850
Rex Power Magnetics 3PR-0002C5H is a three-phase AC line/load reactor rated 2 A continuous, 5% impedance, 22.97 mH per phase, 600 V class. It installs on the input (line) or output (load) side of a variable frequency drive. At 480 V it matches drives rated 1 HP. At 600 V it matches 1 HP.
Specifications
| Catalog number | 3PR-0002C5H (open style). Add /E for enclosed: 3PR-0002C5H/E |
| Rated current | 2 A, three phase |
| Impedance | 5% |
| Inductance | 22.97 mH |
| Voltage class | 600 V max (480 V and 600 V systems) |
| Drive HP at 480 V | 1 HP |
| Drive HP at 600 V | 1 HP |
| Frequency | 60 Hz (50/60 Hz optional) |
| Windings | Copper |
| Insulation | 220°C system, 150°C rise max |
| Overload | 150% of rated current for 1 minute |
| Saturation | Not less than 250% of rated current |
| Sound level | Below 40 dBA |
| Open style dimensions (A/B/C/D/E, in) | 4.25 / 3.00 / 4.375 / 2.875 / 2.625 |
| Open style weight | 5.3 lb |
| Enclosed style | Type 1 enclosure size 0, 9.50 x 7.00 x 8.00 in (L x D x H), approx. 14.3 lb |
| Certifications | CSA certified, UL Listed. IEEE C57.110, NEMA ST-20 |
| Warranty | 12 months |
| Made in | Concord, Ontario, Canada |
3% or 5%?
A 3% reactor is the usual pick on the line side of a drive. It knocks down the current harmonics the drive puts back on the supply and buffers the drive's DC bus from voltage transients. A 5% reactor gives more harmonic attenuation and more transient protection at the cost of a little more voltage drop. On the load side (between drive and motor) either impedance slows the dV/dt at the motor terminals on longer cable runs. The 5% unit on this page pairs with 3PR-0002C3H at the other impedance.
Replacing an MTE, TCI or Hammond reactor?
Send us the part number off the nameplate (MTE RL series, TCI KDR, Hammond Power RM series, or any other). We match amps, impedance and voltage class to the Rex catalog number and quote it, usually the same business day.
Documentation
Rex Power Magnetics Line Reactor Catalog (PDF): selection tables for 208, 240, 480 and 600 V, inductance, dimensions and enclosure drawings.
Common questions
Is 3PR-0002C5H a line reactor or a load reactor?
Both. Rex 3PR series reactors are rated for either side of the drive. Use it as a line reactor for harmonics and transient protection, or as a load reactor to protect the motor on long cable runs.
What size drive does 3PR-0002C5H fit?
Rated 2 A. At 480 V that covers drives at 1 HP. At 600 V, 1 HP. Size to the drive's rated input or output current, not the motor nameplate, when they differ.
Can I get it in an enclosure?
Yes. Order 3PR-0002C5H/E for a Type 1 enclosed unit, size 0 (9.50 x 7.00 x 8.00 in).
Get a quote
Send the part number and quantity for a price, or book 15 minutes to size a reactor for a specific drive and cable run.
Request a QuoteBook 15 Minutes with an Application Engineer
MTE is a trademark of MTE Corporation. TCI and KDR are trademarks of TCI, LLC. Hammond Power Solutions is a trademark of Hammond Power Solutions Inc. Applied Control Inc. is not affiliated with these companies. Competitor names appear only to identify products for comparison. Specifications are from the Rex Power Magnetics catalog and are subject to change; confirm against the current datasheet before installation.