Buck-Boost Transformer Sizing and Cross Reference

Size a buck-boost transformer on load amps, not load kVA. Multiply the load amps by the secondary volts you connect in series, and pick the next VA size up. A 20 A load boosted with a 32 V secondary needs 640 VA, so a 750 VA unit. The cross reference below matches Micron buck-boost units to Acme, Square D, Eaton, GE, HPS, Jefferson, Hevi-Duty and FPC part numbers.

Request a QuoteBook 30 Minutes to Review the ApplicationCall 248-830-4850

The three Micron buck-boost groups

Group Primary Secondary Sizes
A 120 x 240 V 16/32 V 50 VA to 7.5 kVA
B 240 x 480 V 24/48 V 50 VA to 7.5 kVA
C 120 x 240 V 12/24 V 50 VA to 7.5 kVA

How to size it

Step What to do
1 Find the line voltage you have and the voltage the load needs.
2 Pick the group and connection that gets you closest. Example: Group A, primary in series on a 208 V line, secondaries in series, boosts to about 236 V.
3 Find the load amps from the nameplate.
4 Transformer VA = load amps x rated secondary volts in that connection (32 V for Group A secondaries in series).
5 Pick the next standard VA size up. For three phase, Micron banks two units (open delta) or three units.

Worked example: 230 V motor on a 208 V line

Item Numbers Result
Connection Group A, 240 V primary on 208 V, 32 V secondary in series 208 x 272 / 240 = about 236 V out
Load Single phase motor, 20 A
VA needed 20 A x 32 V 640 VA
Pick Next size up, Group A 750 VA, Micron JH750A1EB1A15 (was J750A1EB1A02). Replaces Acme T181059 or Square D 750SV46F

Where Micron says not to use one

Micron says buck-boost units are mainly for motor loads. Do not use one for a motor control circuit, to fix a line that swings up and down, or to get a neutral on a delta system. Use a control transformer or a regular two-winding transformer for those. On a 208Y/120 grounded system, a boost to 240 V leaves 139 V to ground. If you need 240/120 V with a center ground, use a two-winding transformer.

Buck-boost cross reference

Group A: 120 x 240 V primary, 16/32 V secondary

VA Micron (current) Micron (old) Acme Eaton C-H Hevi-Duty FPC GE HPS Jefferson Square D
50 VA JH050A1EB1A14 J050A1EB1A01 T181054 S10N06A81N Ask K1XGF16-0.05 9T51B0122 QC05ESCB 416-1200-000 50SV46A
100 VA JH100A1EB1A14 J100A1EB1A01 T181055 S10N06A82N Ask K1XGF16-0.1 9T51B0124 QC10ESCB 416-1201-000 100SV46A
150 VA JH150A1EB1A14 J150A1EB1A01 T181056 S10N06A83N HS20B150 K1XGF16-0.15 9T51B0125 QC15ESCB 416-1211-000 150SV46A
250 VA JH250A1EB1A14 J250A1EB1A02 T181057 S10N06P26P HS20B250 K1XGF16-0.25 9T51B0127 QC25ESCB 416-1221-000 250SV46B
500 VA JH500A1EB1A14 J500A1EB1A02 T181058 S10N06P51P HS20F500B K1XGF16-0.5 9T51B0128 QC50ESCB 416-1231-000 500SV46B
750 VA JH750A1EB1A15 J750A1EB1A02 T181059 S10N06P76P HS20F750B K1XGF16-0.75 9T51B0129 QC75ESCB 416-1241-000 750SV46F
1 kVA JH001K1EB1A15 J001K1EB1A02 T113073 S10N06P01P HS20F1B K1XGF16-1 9T51B0130 Q1C0ESCB 416-1251-000 1S46F
1.5 kVA JH1X5K1EB1A15 J1X5K1EB1A02 T113074 S10N06P16P HS20F1.5A K1XGF16-1.5 9T51B0131 Q1C5ESCF 416-1261-000 1.5S46F
2 kVA JH002K1EB1A14 J002K1EB1A02 T113075 S10N06P02P HS20F2A K1XGF16-2 9T51B0132 Q002ESCF 416-1271-000 2S46F
3 kVA JH003K1EB1A15 J003K1EB1A03 T113076 S10N06A03N HS20F3A K1XGF16-3 9T51B0133 Q003ESCF 416-1281-000 3S46F
5 kVA JH005K1EB1A15 J005K1EB1A03 T113077 S10N06A05N HS20F5A K1XLF16-5 9T21B1040G02 Q005ESCF 416-1291-000 Ask
7.5 kVA J7X5K1EB1A03 Same T213078 S10N06A07N HS20F7.5A Ask Ask Ask 416-2201-000 Ask

Group B: 240 x 480 V primary, 24/48 V secondary

VA Micron (current) Micron (old) Acme Eaton C-H Hevi-Duty FPC GE HPS Jefferson Square D
50 VA JH050A1KC1A14 J050A1KC1A01 T181061 S20N08A81N Ask K2XGF24-0.05 9T51B0202 QC05DTCB 416-1400-000 50SV82A
100 VA JH100A1KC1A14 J100A1KC1A01 T181062 S20N08A82N Ask K2XGF24-0.1 9T51B0204 QC10DTCB 416-1401-000 100SV82A
150 VA JH150A1KC1A14 J150A1KC1A01 T181063 S20N08A83N HS22B150 K2XGF24-0.15 9T51B0205 QC15DTCB 416-1411-000 150SV82A
250 VA JH250A1KC1A14 J250A1KC1A02 T181064 S20N08P26P HS22B250 K2XGF24-0.25 9T51B0207 QC25DTCB 416-1421-000 250SV82B
500 VA JH500A1KC1A14 J500A1KC1A02 T181065 S20N08P51P HS22F500B K2XGF24-0.5 9T51B0208 QC50DTCB 416-1431-000 500SV82B
750 VA JH750A1KC1A15 J750A1KC1A02 T181066 S20N08P76P HS22F750B K2XGF24-0.75 9T51B0209 QC75DTCB 416-1441-000 750SV82F
1 kVA JH001K1KC1A15 J001K1KC1A02 T137920 S20N08P01P HS22F1B K2XGF24-1 9T51B0210 Q1C0DTCB 416-1451-000 1S82F
1.5 kVA JH1X5K1KC1A15 J1X5K1KC1A02 T137921 S20N08P16P HS22F1.5A K2XGF24-1.5 9T51B0211 Q1C5DTCF 416-1461-000 1.5S82F
2 kVA JH002K1KC1A15 J002K1KC1A02 T137922 S20N08P02P HS22F2A K2XGF24-2 9T51B0212 Q002DTCF 416-1471-000 2S82F
3 kVA JH003K1KC1A15 J003K1KC1A03 T137923 S20N08A03N HS22F3A K2XGF24-3 9T51B0213 Q003DTCF 416-1481-000 3S82F
5 kVA JH005K1KC1A15 J005K1KC1A03 T137924 S20N08A05N HS22F5A K2XLF24-5 Ask Q005DTCF 416-1491-000 Ask
7.5 kVA J7X5K1KC1A03 Same T243570 S20N08A07N HS22F7.5A Ask Ask Ask 416-2401-000 Ask

Group C: 120 x 240 V primary, 12/24 V secondary

VA Micron (current) Micron (old) Acme Eaton C-H Hevi-Duty FPC GE HPS Jefferson Square D
50 VA JH050A1EA1A14 J050A1EA1A01 T181047 S10N04A81N HS19B50 K1XGF12-0.05 9T51B0102 QC05ERCB 416-1100-000 50SV43A
100 VA JH100A1EA1A14 J100A1EA1A01 T181048 S10N04A82N HS19B100 K1XGF12-0.1 9T51B0104 QC10ERCB 416-1101-000 100SV43A
150 VA JH150A1EA1A14 J150A1EA1A01 T181049 S10N04A83N HS19B150 K1XGF12-0.15 9T51B0105 QC15ERCB 416-1111-000 150SV43A
250 VA JH250A1EA1A14 J250A1EA1A02 T181050 S10N04P26P HS19B250 K1XGF12-0.25 9T51B0107 QC25ERCB 416-1121-000 250SV43B
500 VA JH500A1EA1A14 J500A1EA1A02 T181051 S10N04P51P HS19F500B K1XGF12-0.5 9T51B0108 QC50ERCB 416-1131-000 500SV43B
750 VA JH750A1EA1A15 J750A1EA1A02 T181052 S10N04P76P HS19F750B K1XGF12-0.75 9T51B0109 QC75ERCB 416-1141-000 750SV43F
1 kVA JH001K1EA1A15 J001K1EA1A02 T111683 S10N04P01P HS19F1B K1XGF12-1 9T51B0110 Q1C0ERCB 416-1151-000 1S43F
1.5 kVA JH1X5K1EA1A15 J1X5K1EA1A02 T111684 S10N04P16P HS19F1.5A K1XGF12-1.5 9T51B0111 Q1C5ERCF 416-1161-000 1.5S43F
2 kVA JH002K1EA1A15 J002K1EA1A02 T111685 S10N04P02P HS19F2A K1XGF12-2 9T51B0112 Q002ERCF 416-1171-000 2S43F
3 kVA JH003K1EA1A15 J003K1EA1A03 T111686 S10N04A03N HS19F3A K1XGF12-3 9T51B0113 Q003ERCF 416-1181-000 3S43F
5 kVA JH005K1EA1A15 J005K1EA1A03 T111687 S10N04A05N HS19F5A K1XLF12-5 9T21B1037G02 Q005ERCF 416-1191-000 Ask
7.5 kVA J7X5K1EA1A03 Same T211688 S10N04A07N HS19F7.5A Ask Ask Ask 416-2101-000 Ask

Common questions

How do I size a buck-boost transformer?

Multiply the load amps by the rated secondary volts in the connection you use. Pick the next VA size up. A 20 A load on a 32 V boost needs 640 VA, so a 750 VA unit.

Why is a 750 VA buck-boost enough for a 4.7 kVA load?

In buck or boost, the transformer only carries the extra volts, not the whole load. At 236 V and 20 A the load is about 4.7 kVA, but the transformer only handles 32 V x 20 A.

What replaces an Acme T181055?

Micron JH100A1EB1A14, Group A, 100 VA (old number J100A1EB1A01). Same 120 x 240 V primary and 16/32 V secondary.

Can I use a buck-boost on three phase?

Yes. Micron banks two units in open delta or three units. The load amps and the system wiring set how many you need. Send the line voltage, load voltage and amps.

Can a buck-boost give me a neutral?

No. Micron says not to use one to get a neutral on a delta system. Use a two-winding transformer.

Get it crossed and quoted

Send the old part number, or the line voltage, the load voltage and the load amps. We send back the Micron buck-boost part and how to wire it.