Line Reactor vs Load Reactor on a VFD

A line reactor goes on the input of the drive, between the supply and the drive. A load reactor goes on the output, between the drive and the motor. It is the same kind of three phase inductor. Where you put it decides the job. On the input it cuts harmonics and shields the drive from line spikes. On the output it slows the voltage edges and cuts the voltage spikes at the end of a long motor cable.

Request a QuoteBook 30 Minutes to Review the ApplicationCall 248-830-4850

Side by side

Line reactor (drive input) Load reactor (drive output)
Wired to Drive input terminals R/L1, S/L2, T/L3 Drive output terminals U/T1, V/T2, W/T3, then on to the motor
Main job Cuts line current harmonics, soaks up line spikes, cuts nuisance trips Slows dv/dt, cuts peak voltage at the motor, cuts cable charging current
When the drive maker calls for it TECO A510 and F510 manuals: install an AC reactor on the input when the supply is 600 kVA or more. It also improves power factor Long motor cables. Rex says output reactors work on the high frequency effects of long cables
Peak voltage at the motor on a long cable No effect About 200% of applied voltage with no reactor, typically under 150% with a reactor alone (Rex)
Usual impedance 2% or 3%; 4% to 5% for heavy transients or tighter harmonic limits (Rex) 3% or 5%
Where to mount Ahead of the drive, inside the panel Right next to the drive output (Rex note)
Size it by Drive input current at your voltage Drive output current (or the motor current) at your voltage
Lines on this site Block LR3 and Rex 3PR Rex 3PR

Worked example: 40 HP, 480 V drive, 250 ft of motor cable

Step Check Result
Supply size Plant transformer is 1,000 kVA. TECO rule: 600 kVA or more Add a line reactor on the input
Line reactor pick Rex 480 V table: 40 HP is a 60 A reactor. Block cross puts LR3 48-3/63 on 40 HP Rex 3PR-0060C3H (3%) or Block LR3 48-3/63 (3%)
Carrier frequency 250 ft is in the 166 to 328 ft band of the TECO table Set parameter 11-01 to 5 kHz max
Load reactor Long cable, motor peak voltage is the risk Rex 3PR-0060C3H on the output, mounted next to the drive
Peak at the motor Rex figures for a long cable About 200% without, typically under 150% with the reactor. Under 125% needs a Rex Motor Guarding filter
Panel heat Each reactor adds watts to the panel Add the reactor loss to the heat load calculator

Reactor part numbers on this site

Part number Brand Use Rating
LR3 48-3/63 Block Line (input) 63 A, 3% at 480 V, 40 HP
LR3 48-5/63 Block Line (input) 63 A, 5% at 480 V, 40 HP
LR3 48-3/125 Block Line (input) 125 A, 3% at 480 V, 100 HP
3PR-0027C3H Rex Line or load 27 A, 3%, 480/600 V, 15 to 20 HP at 480 V
3PR-0060C3H Rex Line or load 60 A, 3%, 480/600 V, 40 HP at 480 V
3PR-0060C5H Rex Line or load 60 A, 5%, 480/600 V, 40 HP at 480 V
3PR-0080C3H Rex Line or load 80 A, 3%, 480/600 V, 50 to 60 HP at 480 V
3PR-0034C3L Rex Line or load 34 A, 3%, 208/240 V, 10 HP at 208 V

All Block LR3 reactors are in the Block collection and all Rex 3PR reactors are in the Rex Power Magnetics collection. Replacing a Rockwell 1321, MTE or TCI reactor? Use the line reactor cross reference.

Common questions

Can one reactor do both jobs?

Not at the same time. If you need both, buy two. Rex rates its 3PR reactors for the input or the output of a drive. Block lists the LR3 as a line, commutating or power factor reactor, so we put it on the input.

3% or 5%?

Rex says most line reactor jobs need 2% or 3%. Go to 4% or 5% when the line has heavy spikes or you need cleaner line current. The trade is voltage drop: a 5% reactor drops about 5% of the voltage at full current.

My drive has a DC choke. Do I still need a line reactor?

Maybe. A DC choke and an AC line reactor both cut line harmonics, and Rex shows they stack. TECO still calls for an input AC reactor when the supply is 600 kVA or more.

How long can the motor cable be before I need a load reactor?

TECO says to lower the carrier frequency once the cable passes 25 m (82 ft), and caps it at 2 kHz past 329 ft. Long runs also make the voltage spikes at the motor that a load reactor cuts. Send the cable length and motor insulation rating and we size it with you. More in long motor leads on a VFD.

Where does the load reactor go?

Right at the drive output, not at the motor. Rex calls this out in its catalog. Leave room for heat and add its watts to the panel heat load.

Get it sized and quoted

Send the drive model or HP, the supply voltage, the plant transformer kVA and the motor cable length. We send back the Block or Rex part with lead time.