LR3-AE125-483-0 Block Line Reactor, 125 A, 3% Impedance, 480 V, 100 HP, Aluminum

SKU: LR3-AE125-483-0
Request a Quote Book 15 Minutes with an Application Engineer

Priced within one business day. Factory-direct pricing from an authorized rep. Replacing a competitor part? Send the number and we cross it.

Questions or Require Additional Information?

Call us Today at +1-248-830-4850

The Block LR3-AE125-483-0 is a 3 phase line reactor rated 125 A at 480 V with 3% impedance (0.18 mH per phase). Block USA rates it for 100 HP at 480 V. It is the LR3-AE version with aluminum windings, UL 508 Listed and cULus marked, open frame (IP00), class H insulation and bolt terminals. Applied Control is the Block manufacturers' representative. Send the catalog number, or the drive HP, voltage and impedance you need, and we send back a quote.

Request a QuoteBook 30 Minutes to Review the Application

LR3-AE125-483-0 specifications

Catalog number LR3-AE125-483-0
Manufacturer Block Transformatoren-Elektronik (Block USA)
Series LR3-AE line reactor, 3 phase, aluminum winding
Rated current 3 x 125 A AC
Linear current 3 x 187.5 A AC
Inductance 3 x 0.18 mH
Impedance (short circuit voltage) 3% at 480 V
Rated voltage 480 V (voltage range 0 to 690 V)
Frequency 50 to 60 Hz
HP at 480 V (Block USA line reactor brochure) 100 HP
Motor or converter power (Block product page) 75 kW (100.58 HP)
Power loss 260 W
Insulation class H (180 C), UL class 180
Duty cycle 100%
Protection IP00, open core and coil, mount inside an enclosure
Ambient temperature -10 to 40 C (14 to 104 F)
Terminals Bolt connections for line, load and ground
Winding material Aluminum
Dimensions (W x H x D) 400 x 186.5 x 180 mm (15.75 x 7.34 x 7.09 in)
Weight 16.8 kg (37.04 lb)
Standards and listings UL 508 Listed, cULus, EN 61558-2-20, RoHS (EN IEC 63000)

Specifications from the Block product page for LR3-AE125-483-0. HP rating from the Block USA line reactor brochure (2026/27). Confirm against the current datasheet before installation.

LR3-AE or LR3?

Block builds this rating two ways. The LR3-AE125-483-0 has aluminum windings and bolt terminals. The LR3 48-3/125 is the same current and impedance with copper windings and flat copper terminals. Pick by terminal style, panel space and weight. The copper LR3 48-3 parts are the ones on the Block USA cross reference table.

Crossing to LR3-AE125-483-0

The Block USA cross reference table lists the copper LR3 parts, not the LR3-AE. If you have a Rockwell 1321, MTE, TCI, Acme or Hammond Power Solutions part number for a 100 HP, 3% reactor, send it and we confirm whether the LR3-AE125-483-0 or the copper LR3 fits your panel. The full table is on the line reactor cross reference page.

Nearby sizes

Next LR3-AE 3% sizes: LR3-AE100-483-0 and LR3-AE160-483-0.

3% or 5%?

A 3% reactor on the drive input cuts line notching and nuisance overvoltage trips and is the usual default. A 5% reactor cuts input current harmonics further and gives more protection when the supply is stiff or has capacitor switching upstream. On the output side, a reactor slows voltage rise at the motor on longer lead runs. Send the drive model and motor lead length and we will size it with you. See line reactor vs load reactor, the Block collection, TECO AC drives and the cross reference hub.

Request a QuoteBook 30 Minutes to Review the Application

Rockwell Automation, MTE, TCI, Acme and Hammond Power Solutions are trademarks of their respective owners. Applied Control Inc. is not affiliated with these companies. Competitor names appear only to identify products for comparison.