Outdoor Control Panels: Enclosure, Cooling and Heating

An outdoor panel needs a Type 3R, 4 or 4X box, a sealed cooling unit sized with the sun load added, and a heater for cold nights. Sun on a gray box can add about 14 W per square foot of surface. That one number often moves a panel up a cooling size. The steps below give the math and the part numbers.

Request a QuoteBook 30 Minutes to Review the ApplicationCall 248-830-4850

Step 1: Pick the box

Box Rating Example part Use it when
Painted steel Type 4 Hammond 1418N4E12 (24 x 20 x 12 in, gray) Rain, sleet, snow and hose water. Most pump, lift station and site panels
316 stainless steel Type 4X Hammond 1418N4S16B6 (16 x 12 x 6 in) Salt air, road salt spray, chemical plants and wastewater
Fiberglass Type 3R, 4, 4X, 6P, 12 Stahlin CL707W (Classic series) Corrosive outdoor sites. UL 746C (f1) for UV, rated -76 to +274°F

Step 2: Add the sun to the heat load

Sun heats the outside of the box. The inside then has more heat to get rid of. nVent Hoffman publishes these numbers for a gray box:

Item Value
Peak sun over most of the US About 97 W/ft²
Peak sun in the high, dry Southwest About 111 W/ft²
Sun load to hold an ANSI 61 gray box at room temperature About 14 W/ft² of surface
Sun load if the box may run 20°F above room About 6 W/ft² of surface
Rise from sun alone, ANSI 61 gray, no load inside About 40°F
Light from the ground and walls nearby Can add up to 30%

Worked example: 24 x 20 x 12 in pump panel in full sun

Hammond 1418N4E12 box, gray. 200 W of drives and power supplies inside. Hottest day 100°F. Keep the inside at 95°F. All six sides add up to 14 ft².

Step Numbers BTU/hr
Heat from parts 200 W x 3.413 683
Heat in through the walls 1.25 x 14 ft² x 5°F (100 minus 95) 88
Sun 14 W/ft² x 14 ft² = 196 W, x 3.413 669
Total About 1,440
Pick Next size up, Type 3R/4, 115 V Pfannenberg DTS 3061, 13382344351 (2,000 to 3,000 BTU/hr)

Step 3: Cooling that stays sealed

A Filterfan pulls outside air, rain and dust into the box, so it does not fit a Type 4 or 4X panel. Use a closed loop unit with the same rating as the box.

Part Rating Outdoor data
Pfannenberg DTS 3061, 13382344351 (115 V) or 13382341351 (230 V) NEMA 3R/4 Ambient 32 to 131°F. Coated coils and pipes on the outside air side. Set point 50 to 104°F, factory set 95°F
Pfannenberg DTS 3031, 13383144351 (115 V) NEMA 3R/4 900 to 1,300 BTU/hr for small boxes
All enclosure air conditioners Type 12, 3R/4 and 4/4X Side, top and flush mount

Step 4: Heat for cold nights

A Michigan winter can run below 0°F. Drives and displays have a low limit, and a cold box sweats when it warms up. A heater with a thermostat holds the inside above the low limit.

Step Numbers Result
Temperature gap Outside -10°F, inside 41°F: 51°F = 28.3 K
Heat loss 28.3 K x 0.51 (painted steel) x 14 ft² 202 W
Outdoor box Hammond says double it 405 W
Minus parts left on Power supplies and PLC: 50 W 355 W
Pick Next size up at 115 V Hammond FLHTF400A115 or Pfannenberg FLH-TF 400, 17040015407, 400 W

Step 5: Seal the entries and stop the surge

Part Data
AGRO Progress MS 1000.20, M20 nickel-plated brass IP 68 (10 bar) and IP 69, -40 to +100°C. Clamps 8 to 15 mm cable
Citel DAC104US-480D Type 1 SPD, 480 V 3PH delta, In 20 kA, Imax 100 kA, SCCR 200 kA, -40 to +85°C, DIN rail
Citel surge protection Type 1 DIN rail and flange mount models, 120 V to 600 V

Common questions

Is Type 3R enough for an outdoor panel?

Type 3R covers rain, sleet and snow from above. It does not cover hose water or blowing dust. If the panel gets hosed, sits in a dusty yard or near a road with salt spray, use Type 4 or 4X.

How much does the sun add to my cooling load?

For a gray box, nVent Hoffman gives about 14 W per square foot of surface to hold the box at room temperature. A 14 ft² box picks up about 196 W, or 669 BTU/hr. A white or light box picks up less.

Can I put a Filterfan on an outdoor panel?

Not on a Type 4 or 4X panel. The fan pulls outside air, rain and dust through the box. Use a sealed NEMA 3R/4 cooling unit like the Pfannenberg DTS 3061.

Why is there water in my sealed outdoor panel?

Most often a gland, fan or window does not match the box rating. A sealed box can also pull in damp air as it cools at night. Check every entry first, then add a heater with a thermostat to keep the inside above the dew point.

Does the panel need a heater and a cooling unit?

Often, yes, in Michigan. The cooling unit runs in July and the heater runs in January. The DTS 3061 lists 32 to 131°F ambient, so the heater covers the cold side.