Rex Power Magnetics Transformers and Reactors

Dry-type distribution transformers to 900 kVA, K-factor and harmonic mitigating transformers to 1,000 kVA, control transformers from 25 VA, AC line and load reactors from 2 A to 1,250 A, and medium voltage VPI and cast coil power transformers to 15,000 kVA and 46 kV. Built in Concord, Ontario. CSA certified and UL Listed. Quoted by Applied Control within one business day.

Request a QuoteBrowse Rex Reactors

Rex Power Magnetics product lines

Every rating below comes from the current Rex catalog. Standard units are Type 1 or 3R, 150°C rise, copper or aluminum windings, 60 Hz with 50/60 Hz optional, and carry a 12 month warranty. About 85% of what Rex ships is built to a customer spec, so anything outside these ranges is a quote, not a no.

Product line Range Voltage class Where it goes
General purpose isolation transformers 3 to 350 kVA single phase, 5 to 900 kVA three phase 1.2 kV 480 to 208Y/120 panel feeds, machine power, building distribution. DOE 2016 and NRCan 2019
Drive isolation transformers 5 to 900 kVA 1.2 kV Ahead of a VFD to isolate the drive, match voltage and absorb transients. K-4 standard, K-9, K-13, K-20 optional
K-factor rated transformers 3 to 333 kVA single phase, 5 to 1,000 kVA three phase 600 V Panels feeding VFDs, UPS and electronic loads. K-4 through K-20 and beyond, IEEE C57.110
Harmonic mitigating transformers 15 to 1,000 kVA three phase 1.2 kV Multi-drive plants chasing IEEE 519. Zero sequence flux cancellation plus phase shifting, single, dual or triple output
Autotransformers 3 to 333 kVA single phase, 5 to 1,000 kVA three phase 1.2 kV Buck-boost and voltage matching where isolation is not needed. Motor starting autotransformers also available
Encapsulated transformers 3 to 125 kVA single phase, 5 to 150 kVA three phase 600 V Washdown, dusty and outdoor spots. Core and coil potted in polyurethane and silica sand, Type 3R standard, 4 or 4X optional
Industrial control transformers 25 to 7,500 VA single phase 600 V UL, 750 V CSA Panel control power. Epoxy encapsulated, high inrush, primary and secondary fuse kits, DIN rail mount and touch-safe covers optional
AC line and load reactors 2 A to 1,250 A three phase, 3% or 5% 600 V max Drive input for harmonics and transients, drive output for long motor leads. Open or Type 1 enclosed. Selection table below
Motor guarding transient filters Sized to drive 600 V dV/dt and reflected wave protection for VFD-fed motors on long runs
Medium voltage power transformers To 15,000 kVA To 46 kV class VPI, VPE and cast coil. Unit substations, mining, utility, data center, marine. CSA-certified on-site test facility
Specialty Custom Per spec Air core reactors, hazardous location transformers, mini power centers, grounding transformers, RC snubbers, medium voltage control power transformers

Line reactor selection at 480 V

Pick the drive HP, then the impedance. Each catalog number opens a full spec page with inductance, dimensions, weight and the enclosed option. For 208, 240 and 600 V, or above 60 HP, send the drive amps and we size it.

Drive HP at 480 V Amps 3% impedance 5% impedance
1 2 3PR-0002C3H 3PR-0002C5H
1.5, 2 4 3PR-0004C3H 3PR-0004C5H
3, 5 8 3PR-0008C3H 3PR-0008C5H
7.5 11 3PR-0011C3H 3PR-0011C5H
10 17 3PR-0017C3H 3PR-0017C5H
15, 20 27 3PR-0027C3H 3PR-0027C5H
25 34 3PR-0034C3H 3PR-0034C5H
30 45 3PR-0045C3H 3PR-0045C5H
40 60 3PR-0060C3H 3PR-0060C5H
50, 60 80 3PR-0080C3H 3PR-0080C5H

Add /E to any catalog number for the Type 1 enclosed version. Source: Rex Power Magnetics line reactor catalog, 480 V table. 75 to 500 HP (100 A to 600 A) and 600 V ratings quoted on request.

What to send for a transformer quote

kVA, primary and secondary voltage, phase, temperature rise (150°C standard, 115°C or 80°C optional), enclosure (Type 1 or 3R standard, 4 or 4X optional), and any K-factor, electrostatic shield, seismic or thermal sensing requirement. Copper or aluminum windings, your call.

What to send for a reactor quote

Drive HP or rated amps, system voltage, 3% or 5%, line or load side, and whether you need it open or enclosed. If you have an MTE, TCI or Hammond Power part number, send that and we cross it.

Certifications

CSA certified (file LR34493 on distribution units), UL Listed, IEEE C57.12.01 and C57.12.91, NEMA ST-20, ISO 9001:2015. Distribution transformers meet DOE 2016 and NRCan 2019 efficiency. Reactors to IEEE C57.110.

Where the units come from

Designed, wound and tested in Concord, Ontario, with a CSA-certified test lab on site and warehouses in the USA. Rex has built power magnetics since 1972.

Get a Rex Power Magnetics quote

Send the spec and get pricing within one business day, or book 15 minutes to size the unit for the application.

Request a QuoteBook 15 Minutes

Common questions

What does Rex Power Magnetics make?

Dry-type transformers and reactors: general purpose isolation transformers from 3 kVA single phase and 5 kVA three phase up to 900 kVA, K-factor and harmonic mitigating transformers to 1,000 kVA, drive isolation transformers, autotransformers, encapsulated transformers, industrial control transformers from 25 VA to 7,500 VA, AC line and load reactors from 2 A to 1,250 A, and medium voltage VPI and cast coil power transformers up to 15,000 kVA and 46 kV class.

What do I need to send for a Rex transformer quote?

kVA, primary and secondary voltages, single or three phase, temperature rise, enclosure type, and any K-factor, electrostatic shield or seismic requirement. For a reactor, the drive HP or amps, the system voltage and the impedance. Pricing comes back within one business day.

Are Rex transformers UL Listed and DOE 2016 compliant?

Yes. Distribution transformers are CSA certified and UL Listed and meet U.S. DOE 2016 (10 CFR Part 431) and Canadian NRCan 2019 efficiency rules. Reactors are CSA certified and UL Listed to IEEE C57.110 and NEMA ST-20.

Do I need a 3% or a 5% line reactor for my VFD?

3% is the usual line-side choice for harmonic reduction and transient protection. 5% gives more attenuation with slightly more voltage drop. On the load side either impedance protects the motor on long cable runs. Size to the drive's rated current, not the motor nameplate.

Can you cross-reference an MTE, TCI or Hammond Power reactor to Rex?

Yes. Send the part number and we match amps, impedance and voltage class to the Rex 3PR catalog number and quote it, usually the same business day.

MTE is a trademark of MTE Corporation. TCI is a trademark of TCI, LLC. Hammond Power Solutions is a trademark of Hammond Power Solutions Inc. Applied Control Inc. is not affiliated with these companies; names appear only to identify products for comparison. Specifications from Rex Power Magnetics published documentation, subject to change.