J7X5K1EB1A03 Micron 7.5 kVA Buck-Boost Transformer, Group A, 120x240V to 16/32V

SKU: J7X5K1EB1A03
Request a Quote Book 15 Minutes with an Application Engineer

Priced within one business day. Factory-direct pricing from an authorized rep. Replacing a competitor part? Send the number and we cross it.

Questions or Require Additional Information?

Call us Today at +1-248-830-4850

Micron J7X5K1EB1A03 is a 7.5 kVA Group A buck-boost transformer: 120 x 240 V primary, 16/32 V secondary, single phase, 600 V class. Micron has no JH number at 7.5 kVA, so this J number is the current part. It crosses to Acme T213078 and Eaton Cutler-Hammer S10N06A07N.

Request a Quote for J7X5K1EB1A03Book 30 Minutes to Review the Application

J7X5K1EB1A03 specifications

Part number J7X5K1EB1A03
Manufacturer Micron Industries
Type Buck-boost transformer, single phase
Voltage group Group A
Primary 120 x 240 V
Secondary 16/32 V
Rating 7.5 kVA
Insulation class 600 V class
Load amps, boost or buck at 32 V 234.3 A max (VA / 32 V)
Load amps, boost or buck at 16 V 468.7 A max (VA / 16 V)
Dimensions 16 in H x 10 3/8 in W x 9 7/8 in D
Weight 123 lb
Warranty 1 year (Micron)

Cross reference

Brand Part number
Acme T213078
Eaton Cutler-Hammer S10N06A07N
Hevi-Duty HS20F7.5A
Jefferson 416-2201-000

How to use it

In buck or boost, the transformer carries only the added or removed volts. Size it on load amps x secondary volts. Wired as an isolation transformer it gives 16 or 32 VAC. Micron says buck-boost units are mainly for motor loads. Do not use one for a motor control circuit, to fix a swinging line, or to get a neutral on a delta system. On a 208Y/120 grounded system, a boost to 240 V leaves 139 V to ground. For three phase, Micron banks two units (open delta) or three units.

Common questions

Is there a JH number for J7X5K1EB1A03?
No. The 7.5 kVA Group A unit is still sold as J7X5K1EB1A03. We confirm the number on every quote.

What Micron part replaces Acme T213078?
J7X5K1EB1A03, 7.5 kVA, Group A.

How much load can a 7.5 kVA buck-boost carry?
About 234.3 A with the 32 V connection, or 468.7 A with the 16 V connection. Send the line volts, load volts and load amps and we check it.

Related: Buck-boost sizing and full cross reference · Micron control transformers by kVA · Micron · Buck-boost transformers

Request a Quote for J7X5K1EB1A03Book 30 Minutes to Review the Application