JH003K1EB1A15 Micron 3 kVA Buck-Boost Transformer, Group A, 120x240V to 16/32V (replaces J003K1EB1A03)

SKU: JH003K1EB1A15
Request a Quote Book 15 Minutes with an Application Engineer

Priced within one business day. Factory-direct pricing from an authorized rep. Replacing a competitor part? Send the number and we cross it.

Questions or Require Additional Information?

Call us Today at +1-248-830-4850

Micron JH003K1EB1A15 is a 3 kVA Group A buck-boost transformer: 120 x 240 V primary, 16/32 V secondary, single phase, 600 V class. It is the current number for the old Micron J003K1EB1A03. It crosses to Acme T113076 and Square D 3S46F.

Request a Quote for JH003K1EB1A15Book 30 Minutes to Review the Application

JH003K1EB1A15 specifications

Part number JH003K1EB1A15
Replaces Micron number J003K1EB1A03 (discontinued)
Manufacturer Micron Industries
Type Buck-boost transformer, single phase
Voltage group Group A
Primary 120 x 240 V
Secondary 16/32 V
Rating 3 kVA
Insulation class 600 V class
Load amps, boost or buck at 32 V 93.7 A max (VA / 32 V)
Load amps, boost or buck at 16 V 187.5 A max (VA / 16 V)
Weight 65 lb
Warranty 1 year (Micron)

Cross reference

Brand Part number
Micron (old) J003K1EB1A03
Acme T113076
Eaton Cutler-Hammer S10N06A03N
Hevi-Duty HS20F3A
FPC K1XGF16-3
GE 9T51B0133
HPS (Hammond Power Solutions) Q003ESCF
Jefferson 416-1281-000
Square D 3S46F

How to use it

In buck or boost, the transformer carries only the added or removed volts. Size it on load amps x secondary volts. Wired as an isolation transformer it gives 16 or 32 VAC. Micron says buck-boost units are mainly for motor loads. Do not use one for a motor control circuit, to fix a swinging line, or to get a neutral on a delta system. On a 208Y/120 grounded system, a boost to 240 V leaves 139 V to ground. For three phase, Micron banks two units (open delta) or three units.

Common questions

What replaces Micron J003K1EB1A03?
JH003K1EB1A15. Same Group A, 120 x 240 V primary, 16/32 V secondary, 3 kVA.

What Micron part replaces Acme T113076?
JH003K1EB1A15, 3 kVA, Group A.

How much load can a 3 kVA buck-boost carry?
About 93.7 A with the 32 V connection, or 187.5 A with the 16 V connection. Send the line volts, load volts and load amps and we check it.

Related: Buck-boost sizing and full cross reference · Micron control transformers by kVA · Micron · Buck-boost transformers

Request a Quote for JH003K1EB1A15Book 30 Minutes to Review the Application