JH050A1EA1A14 Micron 50 VA Buck-Boost Transformer, Group C, 120x240V to 12/24V (replaces J050A1EA1A01)

SKU: JH050A1EA1A14
Request a Quote Book 15 Minutes with an Application Engineer

Priced within one business day. Factory-direct pricing from an authorized rep. Replacing a competitor part? Send the number and we cross it.

Questions or Require Additional Information?

Call us Today at +1-248-830-4850

Micron JH050A1EA1A14 is a 50 VA Group C buck-boost transformer: 120 x 240 V primary, 12/24 V secondary, single phase, 600 V class. It is the current number for the old Micron J050A1EA1A01. It crosses to Acme T181047 and Square D 50SV43A.

Request a Quote for JH050A1EA1A14Book 30 Minutes to Review the Application

JH050A1EA1A14 specifications

Part number JH050A1EA1A14
Replaces Micron number J050A1EA1A01 (discontinued)
Manufacturer Micron Industries
Type Buck-boost transformer, single phase
Voltage group Group C
Primary 120 x 240 V
Secondary 12/24 V
Rating 50 VA
Insulation class 600 V class
Load amps, boost or buck at 24 V 2 A max (VA / 24 V)
Load amps, boost or buck at 12 V 4.1 A max (VA / 12 V)
Weight 6 lb
Warranty 1 year (Micron)

Cross reference

Brand Part number
Micron (old) J050A1EA1A01
Acme T181047
Eaton Cutler-Hammer S10N04A81N
Hevi-Duty HS19B50
FPC K1XGF12-0.05
GE 9T51B0102
HPS (Hammond Power Solutions) QC05ERCB
Jefferson 416-1100-000
Square D 50SV43A

How to use it

In buck or boost, the transformer carries only the added or removed volts. Size it on load amps x secondary volts. Wired as an isolation transformer it gives 12 or 24 VAC. Micron says buck-boost units are mainly for motor loads. Do not use one for a motor control circuit, to fix a swinging line, or to get a neutral on a delta system. On a 208Y/120 grounded system, a boost to 240 V leaves 139 V to ground. For three phase, Micron banks two units (open delta) or three units.

Common questions

What replaces Micron J050A1EA1A01?
JH050A1EA1A14. Same Group C, 120 x 240 V primary, 12/24 V secondary, 50 VA.

What Micron part replaces Acme T181047?
JH050A1EA1A14, 50 VA, Group C.

How much load can a 50 VA buck-boost carry?
About 2 A with the 24 V connection, or 4.1 A with the 12 V connection. Send the line volts, load volts and load amps and we check it.

Related: Buck-boost sizing and full cross reference · Micron control transformers by kVA · Micron · Buck-boost transformers

Request a Quote for JH050A1EA1A14Book 30 Minutes to Review the Application