JH050A1EB1A14 Micron 50 VA Buck-Boost Transformer, Group A, 120x240V to 16/32V (replaces J050A1EB1A01)
Priced within one business day. Factory-direct pricing from an authorized rep. Replacing a competitor part? Send the number and we cross it.
Questions or Require Additional Information?
Call us Today at +1-248-830-4850
Micron JH050A1EB1A14 is a 50 VA Group A buck-boost transformer: 120 x 240 V primary, 16/32 V secondary, single phase, 600 V class. It is the current number for the old Micron J050A1EB1A01. It crosses to Acme T181054 and Square D 50SV46A.
Request a Quote for JH050A1EB1A14Book 30 Minutes to Review the Application
JH050A1EB1A14 specifications
| Part number | JH050A1EB1A14 |
| Replaces Micron number | J050A1EB1A01 (discontinued) |
| Manufacturer | Micron Industries |
| Type | Buck-boost transformer, single phase |
| Voltage group | Group A |
| Primary | 120 x 240 V |
| Secondary | 16/32 V |
| Rating | 50 VA |
| Insulation class | 600 V class |
| Load amps, boost or buck at 32 V | 1.5 A max (VA / 32 V) |
| Load amps, boost or buck at 16 V | 3.1 A max (VA / 16 V) |
| Weight | 6 lb |
| Warranty | 1 year (Micron) |
Source: FactoryMation Micron buck-boost Group A listing (current JH number, weight, group voltages) and Micron buck-boost product page. Load amps are the standard rule: transformer VA divided by the secondary volts in the connection. We confirm the Micron number and the wiring on every quote.
Cross reference
| Brand | Part number |
|---|---|
| Micron (old) | J050A1EB1A01 |
| Acme | T181054 |
| Eaton Cutler-Hammer | S10N06A81N |
| FPC | K1XGF16-0.05 |
| GE | 9T51B0122 |
| HPS (Hammond Power Solutions) | QC05ESCB |
| Jefferson | 416-1200-000 |
| Square D | 50SV46A |
Source: Micron transformer cross reference MINT16A (January 2016), buck-boost section. Check ratings before you swap. Brand names identify the part being replaced; Applied Control is not affiliated with them.
How to use it
In buck or boost, the transformer carries only the added or removed volts. Size it on load amps x secondary volts. Wired as an isolation transformer it gives 16 or 32 VAC. Micron says buck-boost units are mainly for motor loads. Do not use one for a motor control circuit, to fix a swinging line, or to get a neutral on a delta system. On a 208Y/120 grounded system, a boost to 240 V leaves 139 V to ground. For three phase, Micron banks two units (open delta) or three units.
Common questions
What replaces Micron J050A1EB1A01?
JH050A1EB1A14. Same Group A, 120 x 240 V primary, 16/32 V secondary, 50 VA.
What Micron part replaces Acme T181054?
JH050A1EB1A14, 50 VA, Group A.
How much load can a 50 VA buck-boost carry?
About 1.5 A with the 32 V connection, or 3.1 A with the 16 V connection. Send the line volts, load volts and load amps and we check it.
Related: Buck-boost sizing and full cross reference · Micron control transformers by kVA · Micron · Buck-boost transformers