JH100A1EB1A14 Micron 100 VA Buck-Boost Transformer, Group A, 120x240V to 16/32V (replaces J100A1EB1A01)

SKU: JH100A1EB1A14
Request a Quote Book 15 Minutes with an Application Engineer

Priced within one business day. Factory-direct pricing from an authorized rep. Replacing a competitor part? Send the number and we cross it.

Questions or Require Additional Information?

Call us Today at +1-248-830-4850

Micron JH100A1EB1A14 is a 100 VA Group A buck-boost transformer: 120 x 240 V primary, 16/32 V secondary, single phase, 600 V class. It is the current number for the old Micron J100A1EB1A01. It crosses to Acme T181055 and Square D 100SV46A.

Request a Quote for JH100A1EB1A14Book 30 Minutes to Review the Application

JH100A1EB1A14 specifications

Part number JH100A1EB1A14
Replaces Micron number J100A1EB1A01 (discontinued)
Manufacturer Micron Industries
Type Buck-boost transformer, single phase
Voltage group Group A
Primary 120 x 240 V
Secondary 16/32 V
Rating 100 VA
Insulation class 600 V class
Load amps, boost or buck at 32 V 3.1 A max (VA / 32 V)
Load amps, boost or buck at 16 V 6.2 A max (VA / 16 V)
Weight 8 lb
Warranty 1 year (Micron)

Cross reference

Brand Part number
Micron (old) J100A1EB1A01
Acme T181055
Eaton Cutler-Hammer S10N06A82N
FPC K1XGF16-0.1
GE 9T51B0124
HPS (Hammond Power Solutions) QC10ESCB
Jefferson 416-1201-000
Square D 100SV46A

How to use it

In buck or boost, the transformer carries only the added or removed volts. Size it on load amps x secondary volts. Wired as an isolation transformer it gives 16 or 32 VAC. Micron says buck-boost units are mainly for motor loads. Do not use one for a motor control circuit, to fix a swinging line, or to get a neutral on a delta system. On a 208Y/120 grounded system, a boost to 240 V leaves 139 V to ground. For three phase, Micron banks two units (open delta) or three units.

Common questions

What replaces Micron J100A1EB1A01?
JH100A1EB1A14. Same Group A, 120 x 240 V primary, 16/32 V secondary, 100 VA.

What Micron part replaces Acme T181055?
JH100A1EB1A14, 100 VA, Group A.

How much load can a 100 VA buck-boost carry?
About 3.1 A with the 32 V connection, or 6.2 A with the 16 V connection. Send the line volts, load volts and load amps and we check it.

Related: Buck-boost sizing and full cross reference · Micron control transformers by kVA · Micron · Buck-boost transformers

Request a Quote for JH100A1EB1A14Book 30 Minutes to Review the Application