JH100A1KC1A14 Micron 100 VA Buck-Boost Transformer, Group B, 240x480V to 24/48V (replaces J100A1KC1A01)

SKU: JH100A1KC1A14
Request a Quote Book 15 Minutes with an Application Engineer

Priced within one business day. Factory-direct pricing from an authorized rep. Replacing a competitor part? Send the number and we cross it.

Questions or Require Additional Information?

Call us Today at +1-248-830-4850

Micron JH100A1KC1A14 is a 100 VA Group B buck-boost transformer: 240 x 480 V primary, 24/48 V secondary, single phase, 600 V class. It is the current number for the old Micron J100A1KC1A01. It crosses to Acme T181062 and Square D 100SV82A.

Request a Quote for JH100A1KC1A14Book 30 Minutes to Review the Application

JH100A1KC1A14 specifications

Part number JH100A1KC1A14
Replaces Micron number J100A1KC1A01 (discontinued)
Manufacturer Micron Industries
Type Buck-boost transformer, single phase
Voltage group Group B
Primary 240 x 480 V
Secondary 24/48 V
Rating 100 VA
Insulation class 600 V class
Load amps, boost or buck at 48 V 2 A max (VA / 48 V)
Load amps, boost or buck at 24 V 4.1 A max (VA / 24 V)
Weight 8 lb
Warranty 1 year (Micron)

Cross reference

Brand Part number
Micron (old) J100A1KC1A01
Acme T181062
Eaton Cutler-Hammer S20N08A82N
FPC K2XGF24-0.1
GE 9T51B0204
HPS (Hammond Power Solutions) QC10DTCB
Jefferson 416-1401-000
Square D 100SV82A

How to use it

In buck or boost, the transformer carries only the added or removed volts. Size it on load amps x secondary volts. Wired as an isolation transformer it gives 24 or 48 VAC. Micron says buck-boost units are mainly for motor loads. Do not use one for a motor control circuit, to fix a swinging line, or to get a neutral on a delta system. On a 208Y/120 grounded system, a boost to 240 V leaves 139 V to ground. For three phase, Micron banks two units (open delta) or three units.

Common questions

What replaces Micron J100A1KC1A01?
JH100A1KC1A14. Same Group B, 240 x 480 V primary, 24/48 V secondary, 100 VA.

What Micron part replaces Acme T181062?
JH100A1KC1A14, 100 VA, Group B.

How much load can a 100 VA buck-boost carry?
About 2 A with the 48 V connection, or 4.1 A with the 24 V connection. Send the line volts, load volts and load amps and we check it.

Related: Buck-boost sizing and full cross reference · Micron control transformers by kVA · Micron · Buck-boost transformers