JH250A1KC1A14 Micron 250 VA Buck-Boost Transformer, Group B, 240x480V to 24/48V (replaces J250A1KC1A02)

SKU: JH250A1KC1A14
Request a Quote Book 15 Minutes with an Application Engineer

Priced within one business day. Factory-direct pricing from an authorized rep. Replacing a competitor part? Send the number and we cross it.

Questions or Require Additional Information?

Call us Today at +1-248-830-4850

Micron JH250A1KC1A14 is a 250 VA Group B buck-boost transformer: 240 x 480 V primary, 24/48 V secondary, single phase, 600 V class. It is the current number for the old Micron J250A1KC1A02. It crosses to Acme T181064 and Square D 250SV82B.

Request a Quote for JH250A1KC1A14Book 30 Minutes to Review the Application

JH250A1KC1A14 specifications

Part number JH250A1KC1A14
Replaces Micron number J250A1KC1A02 (discontinued)
Manufacturer Micron Industries
Type Buck-boost transformer, single phase
Voltage group Group B
Primary 240 x 480 V
Secondary 24/48 V
Rating 250 VA
Insulation class 600 V class
Load amps, boost or buck at 48 V 5.2 A max (VA / 48 V)
Load amps, boost or buck at 24 V 10.4 A max (VA / 24 V)
Weight 11 lb
Warranty 1 year (Micron)

Cross reference

Brand Part number
Micron (old) J250A1KC1A02
Acme T181064
Eaton Cutler-Hammer S20N08P26P
Hevi-Duty HS22B250
FPC K2XGF24-0.25
GE 9T51B0207
HPS (Hammond Power Solutions) QC25DTCB
Jefferson 416-1421-000
Square D 250SV82B

How to use it

In buck or boost, the transformer carries only the added or removed volts. Size it on load amps x secondary volts. Wired as an isolation transformer it gives 24 or 48 VAC. Micron says buck-boost units are mainly for motor loads. Do not use one for a motor control circuit, to fix a swinging line, or to get a neutral on a delta system. On a 208Y/120 grounded system, a boost to 240 V leaves 139 V to ground. For three phase, Micron banks two units (open delta) or three units.

Common questions

What replaces Micron J250A1KC1A02?
JH250A1KC1A14. Same Group B, 240 x 480 V primary, 24/48 V secondary, 250 VA.

What Micron part replaces Acme T181064?
JH250A1KC1A14, 250 VA, Group B.

How much load can a 250 VA buck-boost carry?
About 5.2 A with the 48 V connection, or 10.4 A with the 24 V connection. Send the line volts, load volts and load amps and we check it.

Related: Buck-boost sizing and full cross reference · Micron control transformers by kVA · Micron · Buck-boost transformers

Request a Quote for JH250A1KC1A14Book 30 Minutes to Review the Application