Hoffman ATEMNCF and ATEMNOF Thermostat Cross Reference to Pfannenberg FLZ

Hoffman ATEMNCF and ATEMNCC cross to the Pfannenberg FLZ 520, and ATEMNOF and ATEMNOC cross to the FLZ 530. The contact type and the switching ratings match: 15 A at 120 V AC, 10 A at 240 to 250 V AC, 30 W DC. Both snap onto 35 mm DIN rail and use a bimetal sensor. The table lists each Hoffman number.

Request a QuoteBook 30 Minutes to Review the ApplicationCall 248-830-4850

Hoffman to Pfannenberg FLZ

Hoffman Contact and use Pfannenberg, °F dial Pfannenberg, °C dial
ATEMNCF N.C., opens on rise. Heater. °F dial FLZ 520, 17111000010, 32 to 140°F FLZ 520, 17111000000, 0 to 60°C
ATEMNCC N.C., opens on rise. Heater. °C dial FLZ 520, 17111000010, 32 to 140°F FLZ 520, 17111000000, 0 to 60°C
ATEMNOF N.O., closes on rise. Fan. °F dial FLZ 530, 17121000010, 32 to 140°F FLZ 530, 17121000000, 0 to 60°C
ATEMNOC N.O., closes on rise. Fan. °C dial FLZ 530, 17121000010, 32 to 140°F FLZ 530, 17121000000, 0 to 60°C
ATEMNC (older) N.C. Heater FLZ 520, 17111000010 FLZ 520, 17111000000
ATEMNO (older) N.O. Fan FLZ 530, 17121000010 FLZ 530, 17121000000
THERM16F / THERM16C N.C. Heater. 40 to 140°F / 5 to 60°C FLZ 520, 17111000010 FLZ 520, 17111000000
THERM26F / THERM26C N.O. Fan. 40 to 140°F / 5 to 60°C FLZ 530, 17121000010 FLZ 530, 17121000000

Side by side

Hoffman ATEMN series Pfannenberg FLZ 520 / 530
Contact N.C. or N.O., quick acting N.C. (520) or N.O. (530), snap action
At 120 V AC 15 A resistive, 2 A inductive 15 (2) A
At 240 to 250 V AC 10 A resistive, 2 A inductive (250 V) 10 (2) A (240 V)
DC 30 W Max. 30 W
Switching difference 7 K ±4 K Under 7 K, tolerance ±4 K
Sensor Bimetal Bimetal
Mounting 35 mm DIN rail, EN 60715 35 mm DIN rail, EN 60715
Protection IP20 IP 20
Size H x W x D 2.36 x 1.30 x 1.62 in (60 x 33 x 41 mm) 2.83 x 1.57 x 1.42 in (72 x 40 x 36 mm)
Listing cURus E164102, CSA 215952, CE UL, cUL, CSA, CE

Need one part for a fan and a heater?

The Pfannenberg FLZ 510, 17103000000 has a changeover contact. One set point switches a fan on as the cabinet warms, or a heater off. N.C. side: 100 to 250 V AC, 10 (2) A. N.O. side: 100 to 250 V AC, 5 (2) A. For two separate set points, like the Hoffman ADLTEMP dual thermostat, use one FLZ 520 and one FLZ 530, or ask us for the Pfannenberg FLZ 541 / 543 twin thermostat.

Common questions

Is the FLZ 520 a direct replacement for the Hoffman ATEMNCF?

On ratings, yes. Both are N.C. bimetal thermostats for heaters, rated 15 A at 120 V AC and 10 A at 240 to 250 V AC. Use 17111000010 for a °F dial like the ATEMNCF. Check DIN rail space, since the FLZ is a bit larger.

Which one runs a fan?

The N.O. thermostat. Its contact closes as the cabinet warms. That is the Hoffman ATEMNOF or ATEMNOC, and the Pfannenberg FLZ 530.

Where should the thermostat go in the cabinet?

For a heater, Pfannenberg and Hoffman both say to mount it high in the cabinet, as far from heat sources as you can. Keep the vent slots clear.

How do I set it for a heater?

Add the switching difference to the lowest temperature you will allow. Hoffman gives this example: need 5°C (41°F) minimum, add 11 K (7 K + 4 K), set the knob to 16°C (61°F).

Can it switch a 1,000 W heater at 120 V?

1,000 W at 120 V is about 8.3 A, under the 15 A resistive rating. Fan heaters have a motor, so check the inductive rating (2 A) and the heater data. Use a relay for bigger loads.

Get it crossed and quoted

Send the Hoffman catalog number from the label and how many you need. We send back the Pfannenberg part with lead time.

Request a QuoteBook 30 Minutes to Review the ApplicationCall 248-830-4850

Related: Enclosure heaters · Hoffman DAH heater cross · Hoffman filter fan cross · Outdoor panels · Pfannenberg · All cross references