Hoffman Air Conditioner Cross Reference

Hoffman enclosure air conditioners cross to the Pfannenberg DTS series for side mount and the DTT series for top mount. The tables below cover SpectraCool G, SpectraCool Narrow, Slim Fit S, T-series and ProAir CR models, with capacity compared at the 95°F/95°F rating point and the Pfannenberg adapter plate part numbers that make specific retrofits bolt over the existing cutout.

Email a Model Number for a QuoteCall 248-425-9065

Hoffman side mount to Pfannenberg cross reference

Model Published BTU/hr BTU/hr at 95/95 curve Voltages NEMA type Pfannenberg cross
T15-01x6-Gxxx 955 950 115/230 12, 3R, 4, 4X DTS 3021/3031
N16-01x6-Gxxx 955 950 115/230 12, 3R, 4, 4X DTS 3021/3031
N17-01x6-Gxxx 1,025 1,025 115/230/460 12 DTS 3021/3031
S06-03x6-Gxxx 1,430 1,430 115/230 12 DTS 30X1
CR23-02x6-Gxxx 1,600/1,733 115/230 12, 3R, 4, 4X DTS 30X1
N17-02x6-Gxxx 1,800 1,630/1,740 115/230/460 12 DTS 30X1
X23-02x6-Gxxx 2,100/1,900 1,950/1,830 115/230 12, 3R, 4, 4X DTS 30X1
S06-05x6-Gxxx 2,190 2,190 115/230 12 DTS 30X1
T20-02x6-Gxxx 2,200 1,980/1,820 115/230/460 12, 3R, 4, 4X DTS 30X1
N21-02x6-Gxxx 2,200 1,980/1,820 115/230/460 12, 3R, 4, 4X DTS 30X1
CR29-02x6-Gxxx 3,000/2,700 115/230/460 12, 3R, 4, 4X DTS 30X1
G28-04x6-Gxxx 3,410/4,625 3,200/4,400 115/230/460 12, 3R, 4, 4X DTS 31X1 SL
T29-04x6-Gxxx 3,900 3,400 115/230/460 12, 3R, 4, 4X DTS 31X1
CR29-04x6-Gxxx 4,000 115/230/460 12, 3R, 4, 4X DTS 31X1
N28-04x6-Gxxx 4,011/4,291 3,880/4,150 115/230/460 12, 3R, 4, 4X DTS 31X1
S10-10x6-Gxxx 4,710 4,710 115/230/460 12 DTS 31X1 SL
T43-06x6-Gxxx 5,474/5,572 4,920/4,675 115/230/460 12, 3R, 4, 4X DTS 31X5
N36-06x6-Gxxx 5,650/5,650/6,026 5,600/5,250/6,000 115/230/460 12, 3R, 4, 4X DTS 31X5
G28-06x6-Gxxx 6,000/5,685 6,050/5,450 115/230/460 12, 3R, 4, 4X DTS 31X5
CR43-06x6-Gxxx 6,000 115/230/460 12, 3R, 4, 4X DTS 31X5
S10-15x6-Gxxx 6,420 6,420 115/230/460 12 DTS 31X5
N36-08x6-Gxxx 6,739/6,855/6,716 6,650/6,470/6,390 115/230/460 12, 3R, 4, 4X DTS 31X5
G52-08x6-Gxxx 6,800/7,112 6,800/7,112 115/230/460 12, 3R, 4, 4X DTS 32X1
T43-08x6-Gxxx 7,224/6,711 7,100/6,700 115/230/460 12, 3R, 4, 4X DTS 32X1
CR43-08x6-Gxxx 8,000 115/230/460 12, 3R, 4, 4X DTS 32X1
S16-20x6-Gxxx 8,200 8,200 115/230/460 12 DTS 32X1
T43-10x6-Gxxx 9,298/8,381 9,210/8,500 115/230/460 12, 3R, 4, 4X DTS 32X5
S16-25x6-Gxxx 9,560 9,560 115/230/460 12 DTS 32X5
N43-12x6-Gxxx 10,044/9,332 9,650/9,080/9,250 115/230/460 12, 3R, 4, 4X DTS 32X5
G52-12x6-Gxxx 10,700/9,800 11,200/9,800/9,400 115/230/460 12, 3R, 4, 4X DTS 32X5
T50-12x6-Gxxx 10,949 10,850 115/230/460 12, 3R, 4, 4X DTS 32X5
S16-4046-Gxxx 15,400 15,400 460 12 DTS 34X1C
T53-19x6-Gxxx 18,087 17,300 230/460 12, 3R, 4, 4X DTS 34X1C
G57-20x6-Gxxx 18,000/21,400 20,200 230/460 12, 3R, 4, 4X DTS 34X1C
T62-22X6-Gxxx 20,256 20,700 230/460 12, 3R, 4, 4X DTS 34X1C
T70-36x6-Gxxx 36,130 34,900 230/460 12, 3R, 4, 4X Above DTS range, consult
T70-60x6-Gxxx 54,500 51,500 230/460 12, 3R, 4, 4X Above DTS range, consult

The X position in a Pfannenberg DTS model number is the voltage code. Example: DTS 31X1 is the 4,000 BTU/hr side mount family; the exact orderable part number depends on 115, 230 or 460V. Send the voltage and we return the full part number.

Adapter plates for Hoffman retrofits

These Pfannenberg adapter plates cover the existing Hoffman mounting cutout, so the replacement bolts over the opening instead of requiring new panel work. We confirm the plate and unit pairing on the quote.

Hoffman model being replaced Pfannenberg adapter plate P/N
T29-04x6-Gxxx 18380000038
N28-04x6-Gxxx 18380000038
G28-04x6-Gxxx 18380000040
S10-15x6-Gxxx 18380000040
G28-06x6-Gxxx 18380000042
T43-06x6-Gxxx 18380000042
G52-08x6-Gxxx 18380000045
G52-12x6-Gxxx 18380000039

Hoffman top mount to Pfannenberg cross reference

Model Published BTU/hr Voltages NEMA type Pfannenberg cross
MHB11-02x6-Gxxx 2,200 115/230/460 12 DTT 6201
MHB11-04x6-Gxxx 4,000 115/230/460 12 DTT 6301
MHB16-08x6-Gxxx 8,000 230/460 12 DTT 6601

The Pfannenberg DTT top mount range runs from the DTT 6101 at 1,785 BTU/hr to the DTT 6801 at 14,000 BTU/hr. Exact sizing is confirmed against the heat load.

Hoffman suffix decoder

Suffix Configuration
G050 Indoor model
G051 Indoor model, stainless steel (NEMA 4X)
G060 Indoor model with remote access control
G100 Outdoor model without heat package
G101 Outdoor model, partial recess mount
G150 Outdoor model with heat package

Compare capacity at 95°F/95°F, not the nameplate

Enclosure air conditioner ratings are not published at a single standard condition, so nameplate BTU/hr numbers across brands are not directly comparable. The honest comparison is capacity at 95°F ambient and 95°F enclosure temperature, read off the manufacturer's performance curve. A unit sold as 3,900 BTU/hr can deliver 3,400 BTU/hr at the 95/95 point. Every table on this page shows both numbers.

Four things have to line up before a substitution is valid:

  1. Capacity at the rating point. Match 95/95 performance, not marketing BTU.
  2. Voltage. 115, 230 or 460V must match the nameplate.
  3. Enclosure rating. NEMA Type 12, 3R, 4 or 4X on the air conditioner must match the enclosure environment.
  4. Mounting cutout. A capacity cross is not a cutout cross. Pfannenberg adapter plates exist for specific Hoffman retrofits; otherwise plan the panel work.

Also check where the cold air supply sits relative to the hot air return. Several competitor designs place them within 2 to 6 inches of each other, which lets cold discharge short-cycle straight back into the return and cuts effective cooling.

Common questions

What is the Pfannenberg equivalent of a Hoffman SpectraCool air conditioner?

SpectraCool models cross to the Pfannenberg DTS side mount series by capacity at the 95F/95F rating point. For example, the 4,000 BTU/hr class N28 crosses to the DTS 31X1, and the G52 crosses to the DTS 32X1 or DTS 32X5 depending on size. Voltage, NEMA type and cutout still have to be confirmed.

Do adapter plates exist to replace a Hoffman air conditioner with a Pfannenberg?

Yes. Pfannenberg adapter plates cover the existing Hoffman cutout for specific retrofits: P/N 18380000038 for the T29 and N28, P/N 18380000040 for the G28-04 and S10-15, P/N 18380000042 for the G28-06 and T43-06, P/N 18380000045 for the G52-08, and P/N 18380000039 for the G52-12. The plate lets the Pfannenberg unit mount over the existing opening without cutting a new one.

What does the G050 or G150 suffix mean on a Hoffman air conditioner model number?

The suffix identifies the configuration. G050 is the indoor model, G051 is the indoor stainless steel NEMA 4X model, G060 is indoor with remote access control, G100 is the outdoor model without a heat package, G101 is outdoor with partial recess mount, and G150 is the outdoor model with a heat package.

Is the BTU rating on a Hoffman unit directly comparable to a Pfannenberg rating?

Not at the nameplate. Ratings are published at different conditions, so the comparison has to be made at a common point. At 95F ambient and 95F enclosure, a Hoffman T29-04 rated 3,900 BTU/hr delivers 3,400 BTU/hr, and the Pfannenberg DTS 31X1 rated 4,000 delivers 4,100. The tables on this page show both numbers for every model.

Get a cross-referenced quote

Send the model number off the nameplate and the voltage. We come back with the Pfannenberg cross, the adapter plate if one exists for the retrofit, and a price inside 48 hours.

Email: christian.lauderback@appliedcontrolinc.com
Phone: 248-425-9065