Kooltronic enclosure air conditioners cross to the Pfannenberg DTS series for side mount and the DTT series for top mount. The tables below cover the Guardian DP and SP series plus the legacy RP, P and Series units, compared at the 95°F/95°F rating point off the performance curve.

Email a Model Number for a QuoteCall 248-425-9065

Kooltronic side mount to Pfannenberg cross reference

Model Published BTU/hr BTU/hr at 95/95 curve Voltages NEMA type Pfannenberg cross
DP15 (KNA4C1DP15L) 950 950 115 12, 3R, 4, 4X DTS 3021/3031
Micro-Mini (KA4C1.0MML) 1,000 850 115/230 12 DTS 3021/3031
RP17 (KxA4C2RP17R, legacy) 2,000 1,200 115/230 12, 3R DTS 3021/3031
DP17 (KA4C2DP17L, legacy) 2,000 1,500 115 12, 3R DTS 3041
Narrow-Mini (KA4C2.5NML) 2,900 2,100 115 12 DTS 3041
DP21 (KA4C3DP21L) 3,000 2,100 115 12, 3R DTS 3041
DP24 (KxNA4C3DP24L) 3,000 2,200 230/460 12, 3R, 4, 4X DTS 3041
RP28 (K2A4C3RP28R, legacy) 3,000 2,220 115/230 12, 3R DTS 3041
Series 21 (KxNA4C3P21L, legacy) 3,000 2,260/2,160 115/230 4, 4X DTS 3041
DP21 (KNA4C3DP21L) 3,000 2,350 115 12, 3R, 4, 4X DTS 3041
DSP23 (KxA4C2DSP23L) 2,000 2,365 115/230 12, 3R DTS 3041
Series 32 (KxNA4C4P32L, legacy) 4,000 2,650 115/230 4, 4X DTS 31X1
RP33 (KxA4C4RP33R, legacy) 4,000 3,150 115/230 12, 3R DTS 31X1
P24 (K2A4C4P24L, legacy) 3,600 3,600 115/230 12 DTS 31X1
DP33 (KxA4C5DP33L, legacy) 5,000 4,000 115/230 12, 3R DTS 31X1
SP28 (KxNA4C4SP28L) 4,000 4,150 115/230 12, 3R, 4, 4X DTS 31X1
DP33 (KxNA4C5DP33L) 5,000 4,235 115/230 12, 3R, 4, 4X DTS 31X1
RP36 (KxA4C6RP36R, legacy) 6,000 4,500 115/230 12, 3R DTS 31X1 SL
DP38 (K3A4C5DP38L, legacy) 5,000 4,800 460 12, 3R DTS 31X1 SL
DP43 (KxA4C7DP43L, legacy) 7,000 5,500 115/230 12, 3R DTS 31X5
DP33 (KxNA4C5DP33L, 7,000 build) 7,000 5,500 115/230 12, 3R, 4, 4X DTS 31X5
SP36 (KxNA4C6SP36L) 6,000 5,593 115/230 12, 3R, 4, 4X DTS 31X5
Series 38 (K2NA4C7P38L, legacy) 7,000 6,000 115/230 4, 4X DTS 31X5
Series 59 (K2NA4C7P59L, legacy) 7,000 6,000 230 4, 4X DTS 31X5
DP52 (K3A4C7DP52L, legacy) 7,000 6,300 460 12, 3R DTS 31X5
Series 38 / 47 / 59 (K2NA4C10P38L / P47L / P59L, legacy) 10,000 6,700 230 4, 4X DTS 31X5
DP47 (KNA4C5DP47L) 9,000 6,711 115 12, 3R, 4, 4X DTS 32X1
SP36 (KxNA4C8SP36L) 8,000 7,468 115/230 12, 3R, 4, 4X DTS 32X5
DP47L-2 (KNA4C9DP47L-2) 9,000 7,400 115 12, 3R, 4, 4X DTS 32X5
DP47 (KxA4C9DP47L, legacy) 9,000 7,400 115/230 12, 3R DTS 32X5
DP52 (K3A4C9DP52L, legacy) 9,000 8,100 460 12, 3R DTS 32X5
SP43 (KxNA4C11SP43L) 11,000 9,148/9,495 115/230 12, 3R, 4, 4X DTS 32X5
DP47 (K2NA4C5DP47L) 9,632 Not published 230 12, 3R, 4, 4X DTS 32X5
DP50 (KxNA4C5DP50L) 14,000 13,125 230/460 12, 3R, 4, 4X DTS 34X1C
DP53 (KxNA4C5DP53L) 18,000 15,800/16,326 230/460 12, 3R, 4, 4X DTS 34X1C
DP60 (KxNA4C5DP60L) 26,000 18,279/22,242 230/460 12, 3R, 4, 4X DTS 36X1C
EP56 (K2A6C30EP56zR) 30,000 28,000 230 12, 3R Send the heat load, we size it

Pfannenberg DTS part numbers carry a voltage code, so a family name such as DTS 31X1 covers the 115, 230 and 460V builds. Where a 95/95 figure is shown as two or three numbers, they are the 115 / 230 / 460V values in that order. Send the voltage and we return the full orderable part number.

Replacing a legacy Kooltronic unit

A large share of the Kooltronic install base is legacy product. The RP series, the P and Series 21 through Series 59 units, and several early DP builds are marked legacy in the table above. When one fails, the like-for-like replacement path is gone, and the nameplate is a poor guide because the gap between nameplate and 95/95 performance runs wide on these units. The Series 38, 47 and 59 sell as 10,000 BTU/hr and deliver 6,700 at 95/95. Match the 95/95 column instead. Send the full part number off the nameplate and we return the current Pfannenberg DTS unit that covers it, with the mounting approach confirmed on the quote.

Kooltronic top mount to Pfannenberg cross reference

Model Published BTU/hr BTU/hr at 95/95 curve Voltages Pfannenberg cross
KxA4C2.5HSR 2,500 2,085/2,356 115/230 DTT 6201
KxA4C4HTL 4,000 2,250 115/230 DTT 6201
KxA4C5.0H5R 5,000 3,500 115/230 DTT 6201
KA4C6.0H5R-4 / KA4C6.0H6R-4 6,000 3,500 115 DTT 6201
KxA4C6RTL 6,000 6,171/4,600 115/230 DTT 6401
K2A6C12HTL 12,000 11,500 230 DTT 6801 (460V), send the heat load

The Pfannenberg DTT top mount range runs from the DTT 6101 at 1,785 BTU/hr published to the DTT 6801 at 14,000 BTU/hr. The DTT 6601 and DTT 6801 are 460V. Final sizing is confirmed against the heat load on the quote.

Kooltronic part number decoder

Position Meaning
K prefix (voltage) K = 120 VAC, K2 = 230 VAC, K3 = 460 VAC
N in the prefix NEMA 4 and 4X rated build
V suffix NEMA 4X 304 stainless steel cover
(legacy) Discontinued legacy product line

The Pfannenberg DTS side mount range

Pfannenberg model Published BTU/hr BTU/hr at 95/95 curve Voltages NEMA type
DTS 3021/3031 1,200 1,194/1,198 115/230 12, 3R, 4, 4X
DTS 3041 3,000 2,610 115/230/460 12, 3R, 4, 4X
DTS 3061/3081 3,000 2,382 115/230/460 12, 3R, 4, 4X
DTS 31X1 4,000 4,100/4,500 115/230/460 12, 3R, 4, 4X
DTS 31X1 SL 5,000 5,097/5,648/5,301 115/230/460 12, 3R, 4, 4X
DTS 31X5 7,000 6,142/6,995/6,995 115/230/460 12, 3R, 4, 4X
DTS 32X1 8,500 6,825 115/230/460 12, 3R, 4, 4X
DTS 32X5 13,000 11,600/11,000/12,000 115/230/460 12, 3R, 4, 4X
DTS 34X1C 21,000 20,840/20,434 230/460 12, 3R, 4, 4X
DTS 36X1C 29,000 25,181/25,526 230/460 12, 3R, 4, 4X

Compare capacity at 95°F/95°F, not the nameplate

Enclosure air conditioner ratings are not published at a single standard condition, so nameplate BTU/hr numbers across brands are not directly comparable. The honest comparison is capacity at 95°F ambient and 95°F enclosure temperature, read off the manufacturer's performance curve. A unit sold as 3,900 BTU/hr can deliver 3,400 BTU/hr at the 95/95 point. Every table on this page shows both numbers where the curve is published.

Four things have to line up before a substitution is valid:

  1. Capacity at the rating point. Match 95/95 performance, not marketing BTU.
  2. Voltage. 115, 230 or 460V must match the nameplate.
  3. Enclosure rating. NEMA Type 12, 3R, 4 or 4X on the air conditioner must match the enclosure environment.
  4. Mounting cutout. A capacity cross is not a cutout cross. Pfannenberg adapter plates cover specific retrofits; otherwise send the cutout dimensions with the model number and we confirm the mounting approach on the quote.

Also check where the cold air supply sits relative to the hot air return. Several competitor designs place them within 2 to 6 inches of each other, which lets cold discharge short-cycle straight back into the return and cuts effective cooling. Pfannenberg DTS units separate supply and return across the full height of the unit.

Common questions

What replaces a discontinued Kooltronic legacy air conditioner?

The RP series, the P and Series 21 through Series 59 units and several early DP builds are legacy product, marked in the table. When one fails there is no like-for-like path, and the nameplate is a poor guide because the gap to real 95/95 performance runs wide. The Series 38, 47 and 59 sell as 10,000 BTU/hr and deliver 6,700 at 95/95. Send the full part number off the nameplate and we return the current Pfannenberg DTS unit that covers the real operating capacity.

What is the Pfannenberg equivalent of the Kooltronic DP33?

The Pfannenberg DTS 31X1. The current DP33 (KxNA4C5DP33L) publishes 5,000 BTU/hr and delivers 4,235 at the 95F/95F point; the DTS 31X1 delivers 4,100 at 115V and 4,500 at 230V. The legacy DP33 (KxA4C5DP33L) delivers 4,000 at 95/95 and takes the same cross. The 7,000 BTU/hr DP33 build delivers 5,500 and crosses to the DTS 31X5.

What is the Pfannenberg equivalent of the Kooltronic DP47?

It depends on the build. The DP47 (KNA4C5DP47L) delivers 6,711 BTU/hr at 95/95 and crosses to the DTS 32X1. The DP47L-2 and the KxA4C9DP47L deliver 7,400 and cross to the DTS 32X5. Send the full nameplate part number and we return the correct cross.

What does the K prefix mean on a Kooltronic part number?

The prefix is the voltage: K with no digit is 120 VAC, K2 is 230 VAC, K3 is 460 VAC. An N in the prefix indicates the NEMA 4 and 4X rated build, and a V suffix indicates a NEMA 4X 304 stainless steel cover.

Comparing another brand? Start at the enclosure air conditioner cross reference hub.

Get a cross-referenced quote

Send the model number off the nameplate and the voltage. We come back with the Pfannenberg cross, the adapter plate if one exists for the retrofit, and a price inside 48 hours.

Email: christian.lauderback@appliedcontrolinc.com