Hoffman SpectraCool G28 and G52 Cross Reference

The Hoffman SpectraCool G-series crosses to the Pfannenberg DTS side mount series, and every G28 and G52 size has a Pfannenberg adapter plate for a bolt-over retrofit. Capacity is compared below at the 95°F/95°F rating point.

Email a Model Number for a QuoteCall 248-425-9065

SpectraCool G-series to Pfannenberg cross reference

Model Published BTU/hr BTU/hr at 95/95 curve Voltages NEMA type Pfannenberg cross
G28-04x6-Gxxx 3,410/4,625 3,200/4,400 115/230/460 12, 3R, 4, 4X DTS 31X1 SL
G28-06x6-Gxxx 6,000/5,685 6,050/5,450 115/230/460 12, 3R, 4, 4X DTS 31X5
G52-08x6-Gxxx 6,800/7,112 6,800/7,112 115/230/460 12, 3R, 4, 4X DTS 32X1
G52-12x6-Gxxx 10,700/9,800 11,200/9,800/9,400 115/230/460 12, 3R, 4, 4X DTS 32X5
G57-20x6-Gxxx 18,000/21,400 20,200 230/460 12, 3R, 4, 4X DTS 34X1C

The X position in a Pfannenberg DTS model number is the voltage code. Example: DTS 31X1 is the 4,000 BTU/hr side mount family; the exact orderable part number depends on 115, 230 or 460V. Send the voltage and we return the full part number.

Adapter plates for G-series retrofits

Hoffman model being replaced Pfannenberg cross Adapter plate P/N
G28-04x6-Gxxx DTS 31X1 SL 18380000040
G28-06x6-Gxxx DTS 31X5 18380000042
G52-08x6-Gxxx DTS 32X1 18380000045
G52-12x6-Gxxx DTS 32X5 18380000039

The plate covers the existing Hoffman cutout so the Pfannenberg unit mounts over the opening. No new cutout, no blanking plate fabrication.

Compare capacity at 95°F/95°F, not the nameplate

Enclosure air conditioner ratings are not published at a single standard condition, so nameplate BTU/hr numbers across brands are not directly comparable. The honest comparison is capacity at 95°F ambient and 95°F enclosure temperature, read off the manufacturer's performance curve. A unit sold as 3,900 BTU/hr can deliver 3,400 BTU/hr at the 95/95 point. Every table on this page shows both numbers.

Four things have to line up before a substitution is valid:

  1. Capacity at the rating point. Match 95/95 performance, not marketing BTU.
  2. Voltage. 115, 230 or 460V must match the nameplate.
  3. Enclosure rating. NEMA Type 12, 3R, 4 or 4X on the air conditioner must match the enclosure environment.
  4. Mounting cutout. A capacity cross is not a cutout cross. Pfannenberg adapter plates exist for specific Hoffman retrofits; otherwise plan the panel work.

Also check where the cold air supply sits relative to the hot air return. Several competitor designs place them within 2 to 6 inches of each other, which lets cold discharge short-cycle straight back into the return and cuts effective cooling.

Common questions

What is the Pfannenberg equivalent of the Hoffman SpectraCool G28?

The G28-04 crosses to the Pfannenberg DTS 31X1 SL with adapter plate P/N 18380000040, and the G28-06 crosses to the DTS 31X5 with adapter plate P/N 18380000042. At the 95F/95F point the G28-04 delivers 3,200 to 4,400 BTU/hr and the G28-06 delivers 5,450 to 6,050, against 5,097 for the DTS 31X1 SL and 6,995 for the DTS 31X5.

What is the Pfannenberg equivalent of the Hoffman SpectraCool G52?

The G52-08 crosses to the Pfannenberg DTS 32X1 with adapter plate P/N 18380000045, and the G52-12 crosses to the DTS 32X5 with adapter plate P/N 18380000039. At 95F/95F the G52-12 delivers 9,400 to 11,200 BTU/hr and the DTS 32X5 delivers 11,500.

Do the SpectraCool G-series published ratings match the 95F/95F performance?

Not always. The G28-04 publishes 3,410 to 4,625 BTU/hr but delivers 3,200 to 4,400 at the 95F/95F point depending on voltage. Compare both numbers before sizing a replacement; the tables on this page show both.

Can a Pfannenberg unit mount in the existing SpectraCool G-series cutout?

Yes, with the adapter plate. Pfannenberg plates 18380000040, 18380000042, 18380000045 and 18380000039 cover the existing G28 and G52 cutouts so the replacement bolts over the opening without new panel work.

Get a cross-referenced quote

Send the model number off the nameplate and the voltage. We come back with the Pfannenberg cross, the adapter plate if one exists for the retrofit, and a price inside 48 hours.

Email: christian.lauderback@appliedcontrolinc.com
Phone: 248-425-9065